T/CSAE 88-2018Fire safety technical requirements for small electrochemical energy storage power stations (English PDF)
This is a limited preview
Buy now to download the full PDF (7 pages)
Need quotation for your management?
Get a formal quotation for T/CSAE 88-2018 in 30 minutes.
Issued by
China Society of Automotive Engineers
Level / Type
National · Mandatory
Issue date
July 24, 2018
Implementation date
January 1, 1970
Scope
T/CSAE 88-2018 (Fire safety technical requirements for small electrochemical energy storage power stations) is available as an English-translated PDF.
T/CSAE 88-2018 — This standard specifies the fire protection design content and requirements for small electrochemical energy storage power stations. This standard applies to the fire safety design of small electrochemical energy storage power stations.
Found what you need?
Document preview — T/CSAE 88-2018
National Standard of the People's Republic of China
- Classification
- T 36
Issued by: China Society of Automotive Engineers
Contents
- Foreword
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 Electrochemical energy storage power station
- 3.2 Energy storage unit
- 3.3 Small electrochemical energy storage power station
- 3.4 Open frame battery rack
- 3.5 Closed battery rack
- 3.6 Active lithium battery fire suppression device
- 4 Small electrochemical energy storage power station site selection requirements
- 5 Station fire protection requirements
- 6 Energy storage unit safety requirements
- 6.1 Battery rack general fire protection requirements
- 6.2 Open frame battery rack fire requirements
- 6.3 Closed battery rack fire protection requirements
- 7 Active lithium battery fire suppression device requirements
Foreword
This standard was drafted in accordance with the rules given in GB/T 1.1-2009.
Some elements of this standard may involve patents, and the standard issuing authority does not assume responsibility for identifying these patents.
This standard was proposed by the Technical Innovation Alliance of the Electric Vehicle Industry.
This standard was drafted. Shanghai Fire Research Institute of the Ministry of Public Security, Shanghai Automobile City (Group) Co., Ltd., Hangzhou Zhongchuan Fire Equipment Co., Ltd., Wanxiang One Two Three Co., Ltd.
1 Scope
This standard specifies the fire protection design content and requirements for small electrochemical energy storage power stations.
This standard applies to the fire safety design of small electrochemical energy storage power stations.
2 Normative references
The following documents are indispensable for the application of this document. For dated references, only the dated version applies to this file. For undated references, the latest edition (including all amendments) applies to this document.
GB 51048-2014 "Design Specifications for Electrochemical Energy Storage Power Stations" GB 50140 "Design Specification for Construction Fire Extinguisher" GB 50217-2007 "Power Engineering Cable Design Specification" GB/T 18384.3-2001 "Safety requirements for electric vehicles - Part 3. Protection against electric shocks"
3 Terms and definitions
3.1 Electrochemical energy storage power station
An electrochemical cell is used as an energy storage component for power storage, conversion and release.
3.2 Energy storage unit
A minimum energy storage system consisting of a battery pack, a battery management system, and a power conversion system connected thereto.
3.3 Small electrochemical energy storage power station
The capacity of the energy storage unit is above 100kWh, and below 1MWh is a small electrochemical energy storage station.
3.4 Open frame battery rack
The open rack of the battery pack is called an open rack battery rack.
3.5 Closed battery rack
The shelf in which the battery pack is placed is called a closed battery rack.
2T/CSAE 88 -.2018
3.6 Active lithium battery fire suppression device
It is used for automatic detection of lithium battery fire in lithium battery cabinet. It has automatic fire extinguishing medium to suppress lithium battery explosion and fire spread.
Able device.
4 Small electrochemical energy storage power station site selection requirements
4.1 Site selection should not be close to areas with potential fire or explosion hazards. When adjacent to a building that is at risk of explosion or fire, it complies with the provisions of the current national standard GB 50058 "Design Specification for Explosive Hazardous Environmental Power Equipment".
4.2 It is not advisable to choose at the intersection of urban trunk roads and busy traffic sections.
4.3 Small electrochemical energy storage power stations should be set up independently, not less than 10 meters away from the surrounding buildings, and not far from important public buildings.
Less than 25 meters.
4.4 It should not be located in a place with dusty or corrosive gas. When it cannot be far away, it should not be located on the leeward side where the pollution source prevails in the wind direction.
4.5 It should not be located in a place where water may accumulate.
4.6 The design elevation of the site of a small electrochemical energy storage power station should be higher than the flood level with a frequency of 2% or the highest water level in the history.
When the ground design elevation cannot meet the requirements, a reliable water retaining facility or the main equipment base and the indoor floor elevation of the production building should be set.
Higher than the requirement.
4.7 Small electrochemical energy storage power stations should be installed in the area covered by the municipal fire protection pipe network.
5 Station fire protection requirements
5.1 Station buildings should be made of non-combustible materials.
5.2 The battery storage room and the electrical control room in the station should be set independently. If it cannot be set independently, the fire resistance limit should be less than 2h.
Separation of materials, it is not advisable to open the door or open the window on the partition material.
5.3 The battery storage area of the station should be equipped with an explosion-proof accident emergency natural ventilation device, and the ventilation area should be no less than the construction area.
5%; the natural ventilation device should be linked with the fire protection system, and the action time is less than 30s.
5.4 A video surveillance system should be set up in the station, and the video surveillance system should be able to clearly observe the battery cabinet.
5.5 The station building shall be in accordance with the "Severe Dangerous Level" configuration in accordance with the "Code for Design of Fire Extinguishers for Buildings" GB 50140 for fire extinguishers, clean gas fire extinguishers should be used.
5.6 Independent fire power supply should be provided.
5.7 An obvious power cut-off device should be provided. In case of fire, the power supply should be cut off immediately.
5.8 Cable fire prevention and prevention of flame retardation shall comply with the current national standard "Code for Design of Power Engineering Cables" GB 50217-2007 Chapter 7 Relevant regulations.
5.9 The station building should be equipped with an emergency lighting system.
6 Energy storage unit safety requirements
6.1 Battery rack general fire protection requirements
6.1.1 The battery rack shall be constructed of non-combustible materials.
6.3.2 When the battery cabinet is designed in multiple layers, the partitions shall have non-combustible and thermal insulation properties.
6.3.3 The battery rack shall be equipped with an active lithium battery fire suppression device.
3T/CSAE 88 -.2018
6.2 Open frame battery rack fire requirements
6.2.1 Each layer of the battery rack shall be a fire protection unit every 2m or less. The fire protection unit shall be provided with a partition except for the opening facing the walkway.
6.2.2 The opening of the battery frame facing the aisle should be equipped with an emergency linkage fire shutter, and the accident alarm should be in place within 10s.
6.3 Closed battery rack fire protection requirements
6.3.1 The battery rack should be set independently. When it cannot be set independently, it should be separated from other parts by non-combustible materials.
6.3.2 Each sealing unit in the closed battery rack is a fireproof unit.
6.3.3 The battery rack should be as small as possible to reduce the cable opening. The opening part should be sealed with fireproof blocking material, and its technical performance should meet the requirements.
The relevant provisions of Chapter 7 of GB 50217-2007 of "Code for Design of Power Engineering Cables".
6.3.4 An explosion-proof emergency accident closing device shall be installed in the battery rack with ventilated blinds, and no ventilation shutters shall be provided.
Each layer of the battery cabinet shall be provided with a venting surface, and the venting area shall be greater than 5% of the floor area.
7 Active lithium battery fire suppression device requirements
7.1 Active lithium battery fire suppression device should use flammable gas detector to detect battery thermal runaway, each fireproof single of the battery rack Yuan should set up a lot of flammable gas detectors.
7.2 Active lithium battery fire suppression device should be arranged in each fireproof unit of the battery cabinet, gas fire extinguishing should be adopted Agent. Within 10 s after the alarm of the flammable gas detector, the fire extinguishing concentration in the battery cabinet should meet the design requirements.
7.3 Active lithium battery fire suppression device power supply should be set independently.
7.4 Active lithium battery fire suppression device should be equipped with manual/automatic switching device, which is arranged in the station room for easy operation position.
7.5 Active lithium battery fire suppression device should have sound and light alarm function.
7.6 Active lithium battery fire suppression device should be linked with the control center of the site construction unit.
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 7 pages — is available in the English PDF.
Referenced standards
Normative references
- GB 50140Code for Design of Extinguisher Distribution in Buildings
- GB 50217-2007Standard for design of cables of electric power engineering
- GB/T 18384.3-2001[Including 2017-XG1 Modification] Electrically propelled road vehicles -- Safety specifications -- Part 3: Protection of persons against electric shock
GB 51048-2014
How to Download T/CSAE 88-2018
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 50140-2005 — Code for Design of Extinguisher Distribution in Buildings
T/CSAE 143-2020 — Test and assessment specifications for integrated electric drive system of battery electric passenger cars
T/CSAE 144-2020 — Energy efficiency level and test methods for drive motor system and electric drive assembly used on electric vehicles
Secure payment via Stripe
Payments accepted
T/CSAE 88-2018
$294.00