NB/T 10191-2019Compilation method for protective relay optical fiber loop marking (English PDF)
继电保护光纤回路标识编制方法
This is a limited preview
Buy now to download the full PDF (15 pages)
Need quotation for your management?
Get a formal quotation for NB/T 10191-2019 in 30 minutes.
Issued by
NEA
Level / Type
Industry · Recommended
Issue date
June 4, 2019
Implementation date
October 1, 2019
Scope
NB/T 10191-2019 is the English-translated version of 继电保护光纤回路标识编制方法.
NB/T 10191-2019 sets out, for Chinese energy industry use, how to compile the identification labels of relay protection optical fibre circuits in substations and power plants.
It defines Class I fibres running directly between devices, Class II fibres ending at a distribution box or terminal, Class III fibres between distribution frames, spare fibres and the related optical cables, and states which of them need labels at both ends.
Each fibre label carries function information, with local and remote device codes and a function code, above path information giving the optical port codes and cable numbers, in formats shown for every fibre class.
Cable and distribution box labels are also covered. Designers, installers and maintenance staff apply it, and safety automatic devices may follow it for reference. It was issued on 4 June 2019 and has applied since 1 October 2019.
Found what you need?
Document preview — NB/T 10191-2019
National Standard of the People's Republic of China
- ICS
- 29.240.01
- Classification
- K 45
Issued by: National Energy Administration of the People's Republic of China
Contents
- Foreword
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 General requirements for optical fiber loop identification
- 4.1 Identification Classification
- 4.2 Marking scope
- 4.3 Marking requirements
- 5 Requirements for preparing optical fiber labels
- 5.1 Composition of optical fiber label
- 5.2 Requirements for functional information
- 5.3 Requirements for path information
- 5.4 Requirements for the number of the spare fiber
- 5.5 Examples of optical fiber labels
- 6 Requirements for the preparation of optical cable labels
- 6.1 Composition of optical cable label
- 6.2 Requirements for Optical Cable Labels
- 7 Identification requirements for optical fiber distribution box/optical terminal box/optical terminal circuit
- 7.1 Identification of optical fiber distribution box loop
- 7.2 Optical fiber terminal box loop identification
- 7.3 Optical terminal circuit identification
- Appendix A (informative appendix) Examples of function codes
- Appendix B (informative appendix) Examples of optical fiber labels
- Appendix C (Informative Appendix) Examples of Optical Cable Labels
- Appendix D (informative appendix) Examples of circuit identification of optical fiber distribution box/fiber terminal box
Foreword
This standard was drafted in accordance with the rules given in GB/T 1.1-2009.
1 Scope
This standard specifies the classification, scope and compilation requirements for the identification of optical fiber circuits for relay protection.
This standard is applicable to the preparation of the identification of the optical fiber communication circuit for relay protection in substations and power plants, as design, installation, commissioning, acceptance, The basis of operation and maintenance, the identification of optical fiber circuits of substations and power plants safety automatic devices and auxiliary equipment can be implemented by reference.
2 Normative references
The following documents are indispensable for the application of this document. For dated reference documents, only the dated version applies to this document.
For undated references, the latest version (including all amendments) applies to this document.
GB/T 7424 (all parts) Optical cable
GB/T 14733.12 Telecom Terminology Optical Fiber Communication
GB/T 30155 Technical Guidelines for Smart Substation
GB/T 32901 General technical requirements for intelligent substation relay protection
GB/T 34132 General technical requirements for intelligent terminal devices in intelligent substations
DL/T 860 (all parts) Substation communication network and system
DL/T 1777 Technical specification for optical fiber circuit of secondary equipment of intelligent substation
JB/T 2626 The text symbols of commonly used electrical technology in power system relays, protection and automation devices
3 Terms and definitions
GB/T 7424, GB/T 14733.12, GB/T 30155, GB/T 32901, GB/T 34132, DL/T 860, DL/T 1777, JB/T The terms and definitions defined in 2626 and the following apply to this document.
3.1 Optical fiber
A transmission line that guides optical power through a dielectric material, and includes a dielectric material, a buffer layer and a coating.
3.2 Optical fiber loop
The transmission circuit between the equipment (including switches) in the substation and the power plant using optical fiber as the transmission medium is connected by a single optical fiber or multiple optical fibers Continuing connection structure.
3.3 Class I optical fiber
The optical fiber that is directly connected between the equipment does not need to be transferred through the optical fiber distribution box/optical terminal box/optical terminal. According to whether it has a knot in part The structure is divided into ribbon type I optical fiber and non-cable type I optical fiber.
3.4 Class II optical fiber
The optical fiber connected to the optical fiber distribution box/optical terminal box/optical terminal. According to whether part of it has a cable structure, it is divided into cable type II Fiber and non-cable type II fiber.
3.5 Class III optical fiber
Optical fiber connected between optical fiber distribution box/optical terminal box/optical terminal. According to whether it has a cable structure, it is divided into ribbon cable type III optical fiber and Class III optical fiber without cable.
3.6 Standby optical fiber
At least one end is not connected to any equipment or optical fiber distribution box/optical terminal box/optical terminal, and is an optical fiber in a standby state. According to its Whether the part has a cable structure is divided into spare optical fiber with cable and spare optical fiber without cable.
3.7 Class I optical fiber cable
The part of the cable structure with cable I optical fiber.
3.8 Class II optical fiber cable
The part of the cable structure with cable II optical fiber.
3.9 Class III optical fiber cable
The part of the cable structure with cable III optical fiber.
4 General requirements for fiber optic loop identification
4.1 Identification classification
Optical fiber circuit identification is divided into optical fiber label, optical cable label, optical fiber distribution box/optical fiber terminal box/optical terminal circuit identification.
4.2 Marking scope
4.2.1 Type I optical fiber. optical fiber labels should be pasted on both ends.
4.2.2 Type II optical fiber. optical fiber labels should be pasted on both ends.
4.2.3 Type III optical fiber with cable. optical fiber label is not required.
4.2.4 Class III optical fiber without cable. optical fiber labels should be pasted on both ends.
4.2.5 Spare optical fiber. optical fiber labels should be pasted on both ends.
4.2.6 Optical cable. optical cable signs should be hung on the cable structure in the screen cabinets at both ends.
4.2.7 Optical fiber distribution box/optical terminal. there should be a clear loop mark in the eye-catching position or corresponding position.
4.2.8 Optical fiber terminal box. there should be loop identification.
4.3 Labeling requirements
The optical fiber loop identification format should be unified by type and the information should be filled in by type.
5 Requirements for optical fiber labeling
5.1 Composition of optical fiber label
5.1.1 The optical fiber label should include at least function information and path information.
5.1.2 The function information and route information should be on the same label, and the function information should be above the route information.
5.1.3 If the function information and the path information are not on the same label, the function information should be closer to the equipment or optical fiber distribution box/optical Fiber terminal box/optical terminal.
5.1.4 The optical fiber label of the spare optical fiber shall include the information of the spare optical fiber number.
5.2 Requirements for functional information
5.2.1 The function information should include at least the local device code, the opposite device code and the function code, and the format should be as shown in Figure 1.
5.2.2 The equipment code should be unified throughout the site and correspond to the equipment one to one.
5.2.3 The device code of the local/opposite end of the Class I fiber should be the device code of the devices connected at both ends of the fiber.
5.2.4 The device code of the local/opposite end of the Class II fiber should be the device code of the devices connected at both ends of the fiber loop where the fiber is located.
5.2.5 The local/opposite device code of Class III optical fiber should be empty and can be replaced by "-".
5.2.6 If the equipment connected to both ends of the spare fiber has been identified, the code of the spare fiber/opposite device should be the same as 5.2.3, 5.2.4, 5.2.5 /The requirements for the device code of the opposite end are the same; if the spare fiber is not clearly connected to the equipment at both ends, the local/peer device code of the spare fiber should be empty. use... to replace.
5.2.7 The function code should be the uniform description code of the optical fiber loop function of the whole station. See Appendix A for examples.
5.2.8 If the type II optical fiber is pasted with an optical fiber label on the optical fiber distribution box/optical terminal box/optical terminal end, the function information of the optical fiber label of this end shall be The function information of the standby end is the same.
5.3 Requirements for path information
5.3.1 General requirements for path information.
a) The path information should include at least the code of the local optical port and the code of the opposite end optical port. It should include the number of the optical cable and the connection optical Cable number, the format should be as shown in Figure 2.
b) The code number of the optical port should be unified throughout the site and correspond to the optical port one to one.
c) The code of this/opposite optical port should be the optical port of the equipment connected at both ends of the optical fiber, the optical distribution port of the optical fiber distribution box, the optical port of the optical fiber terminal box or Optical port code of the optical terminal.
5.3.2 Path information of cable type I optical fiber.
a) The number of this type of optical fiber cable should be the number of the cable structure of the type I optical fiber;
b) The serial number of the fiber optic cable connected to the end/pair should be empty, which can be replaced by "-";
c) The code of this/opposite optical port should include at least the location number information of the equipment where the optical port is located, the card number information where the optical port is located, and the optical port number information;
d) The path information format of the ribbon-cable type I optical fiber should be shown in Figure 3;
e) Refer to Appendix B.1 for examples of optical fiber labels with cable type I optical fibers.
5.3.3 Path information of Class I fiber without cable.
a) The number of this type of fiber optic cable should be empty and can be replaced by "-";
b) The serial number of the fiber optic cable connected to the end/pair should be empty, which can be replaced by "-";
c) The code of this/opposite optical port should include at least the location number information of the equipment where the optical port is located, the card number information where the optical port is located, and the optical port number information;
d) The path information format of Class I fiber without cable should be shown in Figure 4;
e) Refer to Appendix B.2.for examples of optical fiber labels without cable type I optical fiber. Local optical port code Opposite port code
5.3.4 Path information of cable type II optical fiber.
a) The number of this type of optical fiber cable should be the number of the cable structure of the type II optical fiber;
b) The number of the optical cable connected to the equipment termination should be empty, which can be replaced by "-";
c) The number of the optical fiber distribution box/optical fiber terminal box/optical terminal termination connection optical cable should be in the optical fiber loop where the type II optical fiber is located.
Optical fiber distribution box/optical terminal box/optical terminal, the cable structure number of the optical fiber connected to it; if the optical fiber connected to it If there is no cable structure, the number of the optical cable connected to the end should be empty, which can be replaced by "-";
d) The code of the optical port of the equipment end should include at least the information of the position number of the equipment where the optical port is located, the card number information where the optical port is located, and the information of the optical port number. interest;
e) The optical port code of the optical fiber distribution box/optical terminal box/optical terminal end should at least include the position number of the optical fiber distribution box/optical terminal box Information and optical port/optical terminal box optical port/optical terminal number information;
f) The path information format of the cable type II optical fiber should be shown in Figure 5.
g) Refer to Appendix B.3 for examples of optical fiber identification of cable type II optical fiber.
5.3.5 Path information of non-cable type II optical fiber.
a) The number of this type of fiber optic cable should be empty and can be replaced by "-";
b) The number of the optical cable connected to the equipment termination should be blank, which can be replaced by "-";
c) The number of the optical fiber distribution box/optical terminal box/optical terminal termination connection optical cable should be in the optical fiber loop where the type II optical fiber is located.
Optical fiber distribution box/optical terminal box/optical terminal, the cable structure number of the optical fiber connected to it; if the optical fiber connected to it Without cable structure, the number of the optical fiber distribution box/optical terminal box/optical terminal termination connection optical cable should be empty, which can be replaced by "-";
d) The code of the optical port of the equipment end should include at least the information of the position number of the equipment where the optical port is located, the card number information where the optical port is located, and the information of the optical port number. interest;
e) The optical port code of the optical fiber distribution box/optical terminal box/optical terminal end should at least include the position number of the optical fiber distribution box/optical terminal box Information and optical port/optical terminal box optical port/optical terminal number information;
f) The path information format of non-cable type II optical fiber should be shown in Figure 6.
g) Refer to Appendix B.4 for examples of optical fiber identification for Class II optical fiber without cable.
5.3.6 Path information of cable type III optical fiber.
a) The number of this type of optical fiber cable should be the number of the cable structure of the type III optical fiber;
b) The number of the connecting optical cable of this/pair end shall be the optical fiber loop where the type III optical fiber is located, passing through the optical fiber distribution box/optical terminal box of this end /Optical terminal, the number of the cable structure of the fiber connected to it; if the fiber connected to it has no cable structure, the end is connected The number of the connecting optical cable should be empty and can be replaced by "-";
c) The code of this/opposite optical port should at least include the position number information of the fiber distribution box/fiber terminal box and the optical distribution port/fiber terminal Box optical port/optical terminal number information;
d) The path information format of the ribbon cable type III optical fiber should be shown in Figure 7;
e) Refer to Appendix B.5 for the optical fiber identification example of ribbon cable type III optical fiber.
5.3.7 Path information of III optical fiber without cable.
a) The number of this type of fiber optic cable should be empty and can be replaced by "-";
b) The number of the connecting optical cable of this/pair end shall be the optical fiber loop where the type III optical fiber is located, passing through the optical fiber distribution box/optical terminal box of this end /Optical terminal, the number of the cable structure of the fiber connected to it; if the fiber connected to it has no cable structure, the end is connected The number of the connecting optical cable should be empty and can be replaced by "-";
c) The code of this/opposite optical port should at least include the position number information of the fiber distribution box/fiber terminal box and the optical distribution port/fiber terminal Box optical port/optical terminal number information;
d) The path information format of Class III optical fiber without cable should be shown in Figure 8;
e) Refer to Appendix B.6 for examples of optical fiber identification for Class III optical fiber without cable.
5.3.8 Path information of spare fiber.
a) If both ends of the spare optical fiber are not connected to any equipment or optical fiber distribution box/optical fiber terminal box/optical terminal, the path of the spare optical fiber without cable The path information should be empty and can be replaced by "-"; the path information of the spare fiber with cable should include the cable structure of the spare fiber. number;
b) If one end of the spare optical fiber is connected to the equipment or optical fiber distribution box/optical terminal box/optical terminal, the path information of the spare optical fiber without cable should be Including the optical port code of the equipment connected to the optical fiber or optical fiber distribution box/fiber terminal box/optical terminal, its requirements should be the same as the optical port in 5.3.4 The code requirements are the same; the path information of the spare fiber with cable should include the number of the cable structure of the spare fiber and the equipment connected to the fiber Or the optical port code of the optical fiber distribution box/optical terminal box/optical terminal, the requirements of the optical port code should be the same as the requirements of the optical port code in 5.3.5 Consistent.
5.4 Requirements for spare fiber number
5.4.1 The number of the spare optical fiber shall be uniform throughout the site and correspond to the spare optical fiber one to one.
5.4.2 The numbers at both ends of the same spare fiber should be the same.
5.4.3 Refer to Appendix B.7 for examples of optical fiber labels for spare optical fibers.
6 Requirements for the preparation of optical cable labels
6.1 The composition of the optical cable label
The optical cable label shall contain at least optical cable number information, optical cable specification information and optical cable local/opposite position information. All information shall be in the same label. The format should be as shown in Figure 9.
6.2 Requirements for optical cable label
6.2.1 The number of the optical cable should be uniform throughout the site and correspond to the optical cable one to one.
6.2.2 The optical cable specification information should at least include the number of cores of the optical cable and the multi-mode/single-mode information.
6.2.3 The location information of the local/opposite end of the Type I optical cable should at least include the name and number of the panel where the local/opposite end of the optical cable is located.
6.2.4 The location information of the equipment end of the Type II optical fiber cable should at least include the name and number of the panel where the cable end/opposite end is located.
6.2.5 The position information of the optical fiber distribution box/optical terminal box/optical terminal end of the II type optical fiber cable should at least include the name of the panel where the optical fiber cable itself/opposite end is located Scale, panel number, fiber distribution box/fiber terminal box position number information or optical terminal number information.
6.2.6 The local/opposite end position information of the III type optical cable should at least include the name of the panel where the local/opposite end of the optical cable is located, the panel number, and the optical fiber distribution box / Fiber terminal box position number information or optical terminal number information.
6.2.7 Refer to Appendix C for examples of optical cable labels.
7 Requirements for identification of optical fiber distribution box/optical terminal box/optical terminal circuit
7 Identification requirements for optical fiber distribution box/optical terminal box/optical terminal circuit
7.1 Identification of optical fiber distribution box loop
7.1.1 The loop identification of the optical fiber distribution box shall include at least the position number information of the optical fiber distribution box, the number information of the optical distribution port and the connected optical fiber/optical cable Information.
7.1.2 The position number information of the optical fiber distribution box should correspond to the optical fiber distribution box in this panel.
7.1.3 The circuit identification of the optical fiber distribution box shall clearly identify the corresponding relationship of the optical fiber/optical cable connection on both sides.
7.1.4 Refer to Appendix D for examples of loop identification of optical fiber distribution box.
7.2 Optical fiber terminal box loop identification
7.2.1 The circuit identification of the optical fiber terminal box shall at least include the position number information of the optical fiber terminal box, the optical port number information of the optical fiber terminal box and the connected information. Optical fiber/optical cable information.
7.2.2 The position number information of the optical fiber terminal box shall correspond to the optical fiber terminal box in this screen cabinet.
7.2.3 The circuit identification of the optical fiber terminal box shall clearly identify the corresponding relationship of the optical fiber/optical cable connection on both sides.
7.2.4 Refer to Appendix D for examples of fiber optic terminal box circuit identification.
7.3 Optical terminal circuit identification
7.3.1 The circuit identification of the optical terminal shall include at least the optical terminal number information.
7.3.2 The optical terminal number information should correspond to the optical terminal one by one in this screen cabinet.
Appendix A (Informative appendix)
Function code example Examples of optical fiber label function codes are shown in Table A.1.
Appendix B (Informative appendix) Fiber label example
B.1 Example of ribbon cable type I fiber
An example of an optical fiber label with cable type I optical fiber is shown in Figure B.1.
B.2
Example of Class I fiber without cable
B.3
Example of Type II Fiber with Cable
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.
Referenced standards
Normative references
- GB/T 14733.12Terminology for telecommunication -- Optical communication
- GB/T 30155Technical guide for smart substation
- GB/T 32901General specification for protection relay in smart substation
- GB/T 34132General specification for smart terminal in smart substation
- DL/T 1777Technical specifications for fiber loop of smart substation secondary equipment cabinet
- JB/T 2626Letter symbols for electrical technology for relays, protection and automation equipment of power systems
GB/T 7424 · DL/T 860
Similar standards
How to Download NB/T 10191-2019
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
DL/T 1777-2017 — Technical specifications for fiber loop of smart substation secondary equipment cabinet
DL/T 860.10-2006 — Communication networks and systems in substations. Part 10 Conformance testing
DL/T 860.10-2018 — Communication networks and systems for power utility automation -Part 10: Conformance testing
Secure payment via Stripe
Payments accepted
NB/T 10191-2019