GB/T 47962-2026Guide for the application, specification and testing of phase-shifting transformers (English PDF)

移相变压器的应用、规范和试验导则

Preview PDF

This is a limited preview

Buy now to download the full PDF (33 pages)

Need quotation for your management?

Get a formal quotation for GB/T 47962-2026 in 30 minutes.

Issued by

State Administration for Market Regulation

Level / Type

National · Recommended

Issue date

July 30, 2026

Implementation date

February 1, 2027

Scope

GB/T 47962-2026 is the English-translated version of 移相变压器的应用、规范和试验导则.

GB/T 47962-2026 — This document defines the terminology for phase-shifting transformers and provides information on their functions, applications, operation, protection theories, and design.

The technical content of the surface. This document applies to the application, specifications, operation, factory testing, and field testing of single-phase and three-phase liquid-immersed phase-shifting transformers, and is limited to phase-shifting transformers.

Special considerations for pressure regulators. Note. This document does not apply to general requirements for power transformers as covered in existing standards, recommended practices, or guidelines.

Found what you need?

Document preview — GB/T 47962-2026

National Standard of the People's Republic of China

ICS
29.180
Classification
K 41

Issued by: State Administration for Market Regulation

Contents

  • Preface
  • Introduction
  • 1 Scope
  • 2 Normative References
  • 3 Terms, Definitions, Symbols, and Abbreviations
  • 4 Principles and Applications of Phase-Shifting Transformers
  • 5 Usage conditions
  • 6 Rated data
  • 7 Structure
  • 9 Control System
  • 10 Phase-Shifting Transformer Test
  • 11 Deviation
  • 12 List of Tender Documents
  • Appendix A (Informative) Comparison of this document with IEC 62032:2012 structural numbering
  • References

Foreword

This document complies with the provisions of GB/T 1.1-2020 "Standardization Work Guidelines Part 1: Structure and Drafting Rules of Standardization Documents".

Drafting.

This document is modified to adopt IEC 62032:2012 "Application, specifications and test guidelines for phase-shifting transformers".

This document has undergone significant structural adjustments compared to IEC 62032:2012.A table comparing the structural numbering changes between the two documents is provided.

See Appendix A.

The technical differences between this document and IEC 62032:2012, and the reasons therefor, are as follows.

---The original IEC document is compatible with the technical content of both IEC and IEEE standards. This document only uses the content of the IEC standard.

All technical content related to IEEE standards has been removed to conform to my country's actual situation (see IEC 62032:2012).

IEEE Guide for the Application, Specification, and Testing of Phase Shifting Transformers, Chapter 3, 5.1, 5.2, 5.3, Chapter 6, 6.2, 6.3, Chapter 7, 7.2, 8.1.1, 8.1.2, 8.1.3, 9.3.1.2, 10.1, 10.1.3, 11.1, 11.3);

It includes IEC 60076-1, IEC 60076-3, IEC 60076-5 and IEC 60076-7, and adds normative references.

GB/T 2900.95, GB/T 6451, GB/T 17626.5, GB 50260 and DL/T 860 (all parts) are required to comply with Chinese standards.

Technical requirements (see 3.1, 5.2, 5.3, 5.4.1, 6.1, 6.3.1, 6.4, 7.1, 7.3.1, Chapter 8, 9.3.1.2, 10.1, 10.2.3, 11.1) and 11.3);

---Added symbols and abbreviations; removed footnotes related to the introductory text; removed the term "regulation circuit of phase-shifting transformer" and Definition; The definition of "phase-shifting transformer" has been changed; the terms "single-core phase-shifting transformer" and "two-core phase-shifting transformer" have been replaced.

The terms "single-core design" and "dual-core design" are used; the term "dual-core phase-shifting transformer" has been replaced with the terms "series unit" and "excitation unit".

The definitions of "series unit" and "excitation winding of a two-core phase-shifting transformer" have been modified; "lead-lag switch" has been added.

The terms and definitions of "polarity selector" and "Laryngeal system" are provided in Chapter 3.

---The calculation method for the load phase shift of the phase-shifting transformer was modified, and the phase shift angle diagrams of the phase-shifting transformer under different load conditions were analyzed.

Modifications and additions were made to conform to the actual situation in my country [see 4.3, Figures 3-6, Formulas (3)-16, IEC 62032:2012].

[4.3, Figure 3, Formulas (2) to (4)];

---The increased impedance of the parallel phase-shifting transformers is in accordance with the principle of "considering the base capacity as unchanged" to reflect the actual situation in my country (see 4.7.2);

---The seismic requirements have been modified to suit my country's specific circumstances, increasing the design seismic acceleration and the allowable differential motion between the two oil tanks.

The value requirements must conform to my country's usage conditions [see 5.2d)];

---Increased limits for short-circuit impedance deviation and no-load phase angle deviation at the zero-phase-shift tap position when phase-shifting transformers are operating in parallel, in order to in addition, the limits for the rated voltage ratio deviation and total phase shift angle deviation of adjacent equipment during series operation are specified to clarify the core requirements for series and parallel operation.

Heart-to-heart matching index (see 5.4.2);

---Change the terminal markings of the additional windings to aw, bw, and cw to conform to the actual situation in my country (see 6.2.1, IEC 62032:2012).

---The requirements for control system deviation have been revised, adding factors affecting deviation and stipulations for total deviation, in order to further clarify the control system...

Requirements for statistical deviation (see 9.2.3.1, IEC 62032:2012, 9.2.3);

---The control system now supports new communication protocols and is required to have self-diagnostic faults and remote alarm functions to improve its performance.

Compatibility and ease of operation and maintenance (see 9.2.4);

---The rated voltage of the phase-shifting transformer to which the "Special Operation Impact Test" applies has been changed from "345kV and above" to "330kV".

The specification includes "and above", and adds specific methods for special operation impulse test voltages and the voltages appearing on non-test terminals during the test.

The limits are set to conform to my country's actual conditions, and the test voltage and wiring requirements are further clarified (see 10.3.1.3).

(IEC 62032:2012, 10.2.1.2)

---Added. "Due to the special structure of phase-shifting transformers, deviations exceeding the requirements of GB/T 1094.1 should be resolved through negotiation between the manufacturer and the user." "Commerce" should be adopted to conform to my country's actual situation (see 11.1);

---Added. "Under normal circumstances, the no-load phase angle deviation of each device should not exceed ±0.5°, and the short-circuit impedance deviation should not exceed ±7.5%." the deviation limit takes precedence over general requirements, and the requirement for no-load phase angle deviation is changed from "preferably within 1% of their respective rated phase angles" to...

The change was made to "preferably within ±1% or ±0.1° (whichever is greater) of their respective rated phase shift angles" to strengthen deviation control during parallel operation.

The system is designed to conform to my country's actual conditions (see 11.3, IEC 62032:2012, 11.3.1);

---Added requirements to be specified in the tender document for insulating oil testing (including breakdown voltage, moisture content, dielectric loss, etc.) and partial discharge measurement (induced voltage test).

The test includes a local emission rate <=100 pC and a long-term no-load test (lasting 72 hours, detecting dissolved gases in the oil) to refine the test requirements (see [link]).

12.4.5).

The following editorial changes have been made to this document.

---The formula numbering throughout the text has been changed;

---Replace LTC and OLTC with OLTC or on-load tap changers;

---The content of Chapter 1 has been modified;

---Correct the symbol "VLambda" in the original IEC formula (15) to "Vdelta", and correct the "P=3×deltaV×I=P×2×sin" in formula (17) to "P=3×deltaV×I=P×2×sin".

(alpha/2)" should be corrected to "Pd=3×deltaV×I=PS×2×sin(alpha/2)";

---Explanations have been added to the symbols in the IEC original text 4.5.1 formula;

---Change the footnotes below Table 1 to Table 1;

---The headings of clauses 6.1 and 6.2.1 in the original IEC text have been changed;

---The clause number and clause title of IEC 8.1.1 have been deleted;

---In IEC original texts 4.5, 4.6, 6.1.1 and 10.2.2, the letter subscripts 1, 2, and 3 for the three phases involved in the text and figures are A, B, C, D, E, F, G...

C was replaced;

---Correct the symbols "VSN, VLN" in the original IEC formula (18) to "VS-N, VL-N";

---Appendix A of the original IEC text has been changed to a reference, and its content has been modified accordingly;

---Appendix B of the original IEC text has been deleted.

Please note that some content in this document may involve patents. The issuing organization of this document assumes no responsibility for identifying patents.

This document was proposed by the China Electrical Equipment Industry Association.

This document is under the jurisdiction of the National Technical Committee on Transformer Standardization (SAC/TC44).

Introduction

Existing transformer standardization documents do not cover the terminology, functions, applications, operation, protection theory, and design of phase-shifting transformers.

This document provides guidance for those who standardize, design, and use phase-shifting transformers.

This document describes the application, specifications, and testing of phase-shifting transformers. It is primarily applicable to the following areas.

---The organization responsible for the application and standardization of phase-shifting transformers in power transmission systems to control power flow;

---The organization responsible for testing phase-shifting transformers.

This document is intended to help organizations.

---Understand the different types of phase-shifting transformers and how to apply them to achieve the desired power flow control;

---Standardize the procurement of phase-shifting transformers;

---Standardize the test items and test methods for phase-shifting transformers.

This document aims to achieve the following objectives.

---Promoting consistency in the application and specifications of phase-shifting transformers across organizations;

---This helps in understanding the terminology, types, structure, and testing related to phase-shifting transformers;

---Promote the standardization of phase-shifting transformer test procedures.

1 Scope

This document defines the terminology for phase-shifting transformers and provides information on their functions, applications, operation, protection theories, and design.

The technical content of the surface.

This document applies to the application, specifications, operation, factory testing, and field testing of single-phase and three-phase liquid-immersed phase-shifting transformers, and is limited to phase-shifting transformers.

Special considerations for pressure regulators.

Note. This document does not apply to general requirements for power transformers as covered in existing standards, recommended practices, or guidelines.

2 Normative references

The contents of the following documents, through normative references within the text, constitute essential provisions of this document. Dated citations are not included.

For references to documents, only the version corresponding to that date applies to this document; for undated references, the latest version (including all amendments) applies.

This document.

GB/T 1094.1 Power Transformers - Part 1: General (GB/T 1094.1-2013, IEC 60076-1:2011, MOD) GB/T 1094.3 Power Transformers - Part 3: Insulation Levels, Insulation Tests and External Insulation Air Gap (GB/T 1094.3-2017, IEC 60076-3:2013, MOD) GB/T 1094.5 Power Transformers - Part 5: Short Circuit Withstand Capacity (GB/T 1094.5-2008, IEC 60076-5) 2006, MOD) GB/T 1094.7 Power Transformers - Part 7: Load Guidelines for Oil-Immersed Power Transformers (GB/T 1094.7-2024) IEC 60076-7:2018, MOD) GB/T 2900.95 Electrical Engineering Terminology. Transformers, Voltage Regulators and Reactors (GB/T 2900.95-2015, IEC 60050-421) 1990, NEQ) GB/T 17626.5 Electromagnetic compatibility testing and measurement techniques - Surge (impulse) immunity test (GB/T 17626.5-2019) IEC 61000-4-5:2014, IDT GB 50260 Code for Seismic Design of Power Facilities DL/T 860 (All Parts) Substation Communication Networks and Systems

3 Terms, definitions, symbols and abbreviations

3.1 Terms and Definitions

The terms and definitions defined in GB/T 2900.95 and the following terms and definitions apply to this document.

3.1.1

Phase-shifting transformer (PST) A transformer connected to the power grid via two sets of terminals (or a combination of transformers designed to work together) can change the electrical current between the two sets of terminals.

Pressure phase angle relationship.

Note. The voltage amplitudes at both ends may be equal or unequal. Furthermore, a phase-shifting transformer can also change the voltage of the current phase.

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 33 pages — is available in the English PDF.

Referenced standards

How to Download GB/T 47962-2026

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
33 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 47962-2026

$545.00