GB/T 46131-2025Technical requirements and test methods for tap-changer for ultra high voltage transformers (English PDF)

特高压变压器用分接开关技术要求与试验方法

Open the GB/T 46131-2025 preview as PDF

Preview — first pages of GB/T 46131-2025 (full document: 18 pages)

This is a limited preview

Buy now to download the full PDF (18 pages)

Issued by

SAMR; SAC

Level / Type

National · Recommended

Issue date

August 29, 2025

Implementation date

December 1, 2025

Scope

GB/T 46131-2025 is the English-translated version of 特高压变压器用分接开关技术要求与试验方法.

GB/T 46131-2025 is the Chinese national standard covering the tap changer inside a 1000 kV transformer — the ambient and oil temperature range and the tilt and seismic conditions it works under, the rated current, the insulation level, the regulating range and the short-circuit withstand, the separate requirements and test programmes for the no-load and the on-load type, the mechanical and electrical life that sets when the core has to be lifted, and the seismic test method. First edition, under the China Electricity Council. In force from 1 December 2025. Issued on 29 August 2025, it has been in force since 1 December 2025.

Document preview — GB/T 46131-2025

National Standard of the People's Republic of China

ICS
29.020
Classification
F 21

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • PrefaceIII
  • 1 Scope1
  • 2 Normative References1
  • 3 Terms and Definitions1
  • 4 Basic Requirements1
  • 5 Parameter Requirements2
  • 6 Technical requirements for non-excitation tap changers3
  • 7 No-load tap changer test 6.11
  • 8 Technical requirements for on-load tap changers11
  • 9 On-load tap changer test14
  • 10 Marking, Packaging, Transport and Storage 25.27
  • Appendix A (Informative) Arrangement of Forward and Reverse Adjustment Contacts for Unloaded Tap Changers in UHV AC Autotransformers27
  • Appendix B (Normative) Seismic Test Method for Tap Changers of UHV AC Transformers30

Foreword

This document complies with the provisions of GB/T 1.1-2020 "Standardization Work Guidelines Part 1: Structure and Drafting Rules of Standardization Documents". Drafting.

Please note that some content in this document may involve patents. The issuing organization of this document assumes no responsibility for identifying patents.

This document was proposed by the China Electricity Council.

This document is under the jurisdiction of the National Technical Committee on Standardization of Ultra-High Voltage AC Transmission (SAC/TC569).

This document was drafted by: China Electric Power Research Institute Co., Ltd., Shanghai Huaming Electric Equipment Manufacturing Co., Ltd., and TBEA Hengyang.

Transformer Co., Ltd., Baoding Tianwei Baobian Electric Co., Ltd., State Grid Sichuan Electric Power Research Institute, State Grid Shandong Electric Power Research Institute Electric Power Research Institute of China Electric Power Corporation, TBEA Shenyang Transformer Group Co., Ltd., Xi'an XD Transformer Co., Ltd., and Kaide Trade Co., Ltd.

Yi (Shanghai) Co., Ltd., Hefei Hitachi Energy Transformer Co., Ltd., State Grid Jiangxi Electric Power Research Institute, State Grid Zhejiang Jiangxi Electric Power Research Institute, State Grid Hunan Electric Power Research Institute, State Grid Henan Electric Power Company Electric Power Research Institute, State Grid Hubei Electric Power Company Electric Power Research Institute, State Grid Anhui Electric Power Company Electric Power Research Institute Shandong Electric Power Equipment Co., Ltd., State Grid Shanxi Electric Power Research Institute, Chongqing Hitachi Energy Transformer Co., Ltd., State Grid...

Shanghai Electric Power Research Institute, State Grid Hunan Electric Power Co., Ltd. Ultra-High Voltage Substation Company, China Southern Power Grid Co., Ltd.

State Grid Corporation of China.

The main drafters of this document are: Wang Shaowu, Zhang Shuqi, Wang Ke, Li Peng, Li Jinzhong, Li Geqi, Du Xiuming, Qiao Mu, Sun Jiantao, and Li Xianwei.

Zhao Feng, Sun Shubo, Liu Xueli, Li Gang, Zhang Zhiyong, Ye Zhuangzhuang, Hu Wenbin, Sun Gongsheng, Luo Xinyu, Yang Zhi, Zhu Mengzhao, Xu Puming, Dong Dalei Wu Xingwang, Chai Mengdong, Yu Hua, Wei Yihua, He Lin, Zhou Kai, Wang Peng, Wang Yilin, Sun Wei, Li Wenzhi, Wang Yuwei.

Technical requirements for tap changers used in ultra-high voltage transformers With test methods

1 Scope

This document specifies the basic requirements, parameter requirements, technical requirements, marking, packaging, and transportation of tap changers for 1000kV AC transformers.

It covers topics such as storage and describes the corresponding experimental methods.

This document applies to the design and acceptance of tap changers for 1000kV AC transformers (including autotransformers and step-up transformers).

2 Normative references

GB/T 2900.95

GB/T 4208

GB/T 4797.4

GB/T 10230.1-2019

GB/T 10230.2

GB/T 17623

GB/T 42558.1

GB 50260

3 Terms and Definitions

The terms and definitions defined in GB/T 2900.95 and GB/T 10230.1-2019 apply to this document.

4 Basic Requirements

4.1 Environmental Requirements

4.1.1 The operating temperature range for on-load tap changers in transformer oil is -25°C to 105°C, and the ambient temperature range is -25°C~ 40°C. The operating temperature range for the no-load tap changer in transformer oil is -40°C to 105°C, and the ambient temperature range is -40°C. 40°C.

4.1.2 The electric mechanism should be able to operate normally under outdoor condensation and precipitation conditions.

4.1.3 The sunlight radiation in the operating environment of the tap changer shall comply with the relevant provisions of GB/T 4797.4.

4.1.4 The seismic fortification intensity of the tap changer should be consistent with that of its corresponding transformer.

4.2 Usage Requirements

4.2.1 The tap changer is installed in the voltage regulating and compensation transformer of the UHV step-up transformer or UHV autotransformer, with an inclination of [insert angle here] relative to the ground. It should not exceed 2%.

4.2.2 The tap changer can adopt the neutral point forward and reverse voltage adjustment method. The contact arrangement is shown in Appendix A.

4.2.3 The tap changer should have both manual and electric adjustment functions.

4.2.4 Tap changers installed after the voltage regulating compensation transformer of UHV step-up transformers or UHV autotransformers are non-excitation tap changers.

The deviation between the resistance value of the transformer and the design value should not exceed 2%, and the on-load tap changer and transformer should not malfunction during operation.

4.3 Special Requirements

Other special environmental and usage requirements should be specified when ordering.

5 Parameter Requirements

5.1 Parameters of tap changers for UHV autotransformers

The parameters of the tap changer for the UHV autotransformer should meet the requirements of Table 1.

Table 1.Parameter Table of Tap Changers for UHV Autotransformers Serial Number Parameter Unit No-load tap changer characteristic value On-load tap changer characteristic value

1 Voltage regulation position - Neutral point

2 Phases - Single-phase

3 Maximum rated current Irm A 2400 2000

4 Rated voltage kV - >=4

5 Rated frequency (Hz) 50 50

6 Maximum voltage of the equipment Um kV 126 126

7 Rated insulation level

Rated withstand test voltage (square) Root value) kV 230 230 Lightning full-wave impulse voltage (peak value) kV 550 550

8 Voltage regulation range (kV). 525/3±4x1.25% 525/3±10x0.5%

9 Short-circuit current withstand capability

Thermal stability current (RMS value) (3s) kA 30 24 Dynamic steady-state current (peak value) (0.25s) kA 75 60

10 Mechanical lifespan. 20,000 to 800,000 cycles

11 Electrical lifespan -.200,000 cycles

12 Conditions for core lifting maintenance - -

Running for more than 6 years or More than 100,000 repetitions

13 Partial discharge pC 10 10

14 Temperature rise limit K in contact oil under temperature rise test current 15 15 Note. "-" indicates no content.

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 18 pages — is available in the English PDF.

Referenced standards

Editions of GB/T 46131

EditionTitleRevisionStatus
GB/T 46131-2025Technical requirements and test methods for tap-changer for ultra high voltage transformerscurrent editionCurrent

This page sells the current edition, GB/T 46131-2025. Earlier editions are listed for reference only.

How to Buy GB/T 46131-2025

  1. 1Add to cart. Click the "Buy GB/T 46131-2025" button on this page. You can add more standards before checkout.
  2. 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
  3. 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
  4. 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
18 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 46131-2025

$320.00

$270.00for partners