GB/T 42001-2022Altitude correction method for external insulation flashover voltage of high voltage power transmission projects (English PDF)

高压输变电工程外绝缘放电电压海拔校正方法

Preview PDF

This is a limited preview

Buy now to download the full PDF (15 pages)

Need quotation for your management?

Get a formal quotation for GB/T 42001-2022 in 30 minutes.

Issued by

SAMR; SAC

Level / Type

National · Recommended

Issue date

October 14, 2022

Implementation date

May 1, 2023

Scope

GB/T 42001-2022 is the English-translated version of 高压输变电工程外绝缘放电电压海拔校正方法.

GB/T 42001-2022 describes how the external insulation discharge voltage of high voltage transmission and transformation works is corrected for altitude, both for air gap discharge voltage and for insulator pollution flashover voltage, on 110 kV to 750 kV and plus or minus 400 kV to plus or minus 800 kV transmission lines, substations and converter stations.

Its contents list runs through the correction procedure, then the transmission line air gap, the substation air gap, the converter station air gap and the insulator external insulation.

Clause 1 applies it to projects at altitudes of 5000 m and below, with higher areas referring to it. It defines a high altitude area as one at an altitude of not less than 1000 m, and quotes GB/T 311.1 and GB/T 16927.1. Issued 14 October 2022, applied from 1 May 2023.

Found what you need?

Document preview — GB/T 42001-2022

National Standard of the People's Republic of China

ICS
29.080.01
Classification
F 21

Issued by: State Administration for Market Regulation; Standardization Administration of the PRC

Contents

  • Preface
  • 1 Scope
  • 2 Normative references
  • 3 Terms and Definitions
  • 4 External insulation discharge voltage altitude correction procedure
  • 5 Altitude correction for air gap discharge voltage of transmission line
  • 6 Altitude correction of air gap discharge voltage in substation
  • 7 Altitude correction of air gap discharge voltage of converter station
  • 8 Altitude correction of insulator outer insulation discharge voltage

Foreword

This document is in accordance with the provisions of GB/T 1.1-2020 "Guidelines for Standardization Work Part 1: Structure and Drafting Rules of Standardization Documents" drafted.

1 Scope

This document describes the air gap discharge of 110kV~750kV and ±400kV~±800kV transmission lines, substations, converter stations, etc.

Altitude correction method for electric voltage and insulator pollution flashover discharge voltage.

This document is applicable to the altitude correction of the external insulation discharge voltage of power transmission and transformation projects in areas with an altitude of 5000m and below, and the altitude is 5000m. Refer to the above regions for use.

2 Normative references

The contents of the following documents constitute essential provisions of this document through normative references in the text. Among them, dated citations documents, only the version corresponding to that date applies to this document; for undated references, the latest edition (including all amendments) applies to this document.

GB/T 311.1 Insulation Coordination Part 1: Definitions, Principles and Rules

GB/T 16927.1 High Voltage Test Technology Part 1: General Definitions and Test Requirements

GB/T 16927.2 High Voltage Test Technology Part 2: Measurement System

3 Terms and Definitions

The following terms and definitions apply to this document.

3.1 External insulation

The exposed surface of the air gap or solid insulation of the equipment exposed to the voltage.

3.2 High altitude area

Areas with an altitude of not less than 1000m.

3.3

According to the difference in dielectric strength between the average atmospheric conditions at the altitude and the standard reference atmospheric conditions during operation, the insulation coordination withstand voltage or discharge Factor for electrical voltage correction.

3.4 standard reference atmospheric conditions

Atmospheric conditions for which the standardized withstand voltage applies.

Note: The standard reference atmospheric conditions are temperature 20°C, pressure 101.3kPa, and absolute humidity 11g/m³.

4 External insulation discharge voltage altitude correction procedure

4.1 Positive conversion

Through altitude correction, the external insulation discharge voltage of power transmission and transformation projects in high altitude areas can be converted to the standard reference atmospheric condition of 0m above sea level

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 15 pages — is available in the English PDF.

Referenced standards

Similar standards

How to Download GB/T 42001-2022

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
15 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 42001-2022

$210.00