GB/T 41135.2-2021Current and voltage sensors or detectors, to be used for fault passage indication purposes - Part 2: System aspects (English PDF)
Also coversGBT41135.2-2021
Open the GB/T 41135.2-2021 preview as PDF
This is a limited preview
Buy now to download the full PDF
Issued by
State Administration for Market Regulation, China National Standardization Administration
Level / Type
National · Recommended
Issue date
December 31, 2021
Implementation date
July 1, 2022
Scope
GB/T 41135.2-2021 (Current and voltage sensors or detectors, to be used for fault passage indication purposes - Part 2: System aspects) is available as an English-translated PDF.
GB/T 41135.2-2021 — This document describes electrical phenomena and power system responses during faults according to the most widely used distribution system architectures and fault topologies, This defines the functionality of the Fault Path Indicator (FPI) and the Power Distribution Unit (DSU) (including current and/or voltage sensors for the FPI, DSU) sexual requirements: FPI and DSU are a single device or a combination of multiple devices/functions that can be used to detect faults and indicate the location of the fault: This document is intended to guide the user according to the adopted scheme and operating rules (which are customary, and/or depend on national statutes to provide Constraints on electrical continuity and power quality), selecting the appropriate FPI/DSU and proper operating scheme: Note 1: Fault location refers to the location relative to the FPI/DSU installation point in the grid (upstream or downstream of the FPI/DSU location) or the fault current through the FPI/DSU Orientation of DSU: Considering the characteristics and operating conditions of the power system with the FPI/DSU installed, the fault location can be: --- Derived directly from the FPI/DSU, or; ---From a centralized system that uses more FPI or DSU information: Note 2: This document mainly focuses on the system response during the fault, which is classified by the FPI/DSU fault detection capability level described in GB/T 41135:1 "Core basis", all the requirements in GB/T 41135:1 are specified in detail:
Document preview — GB/T 41135.2-2021
National Standard of the People's Republic of China
- Classification
- K 41
Issued by: State Administration for Market Regulation, China National Standardization Administration
Contents
- foreword
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and Definitions
foreword
This document is in accordance with the provisions of GB/T 1:1-2020 "Guidelines for Standardization Work Part 1: Structure and Drafting Rules of Standardization Documents"
drafted:
This document is Part 2 of GB/T 41135 "Current and Voltage Sensors or Detectors for Fault Path Indication": GB/T 41135
The following sections have been published:
--- Part 1: General principles and requirements;
--- Part 2: System applications:
This document uses the redrafted method to modify the use of IEC 62689-2:2016 "Current and voltage sensors or detectors for fault path indication
Part 2: System Applications":
The technical differences between this document and IEC 62689-2:2016 and their reasons are as follows:
--- In order to adapt to my country's national conditions, the normative references in Chapter 2 are replaced by GB/T 41135:1, which has been modified and adopted international standards:
IEC 62689-1:
The following editorial changes have also been made to this document:
--- The scope has been rewritten;
--- In order to adapt to my country's national conditions, the content of Note 2 in 3:1:1 has been deleted;
--- Correct the error in the IEC standard, in paragraph 1 of 5:2:3:4 (5:2:5 in this document), change "see 5:2:4" to "see 5:2:4"
Figure 3"; in paragraph 1 of 5:2:4:2 (5:2:6:2 in this document), delete "Figure 21"; in Figure A:4 and formula (A:13), use
"I
2,rsd" replaces "I" in the IEC standard
2,0"; in paragraph 9 of B:1, use "A2(FPI/DSU 2)" and "A3(FPI/
DSU 3)" replaces "A3 (FPI/DSU 3)" and "A4 (FPI/DSU 4)" in the IEC standard, respectively:
In the latter paragraph, replace "FPI/DSU (A1 or A2)" in the IEC standard with "FPI/DSU (A2 or A3)";
--- Adjust 5:2:3:3 and 5:2:3:4 of the IEC standard to 5:2:4 and 5:2:5 respectively, and the numbers of other clauses shall be extended in turn;
---Improved the symbols and descriptions of some electrical graphics;
--- The formulas in Appendix A are numbered uniformly;
--- References have been adjusted:
Please note that some content of this document may be patented: The issuing agency of this document assumes no responsibility for identifying patents:
Introduction
0:1 Overview
GB/T 41135 is a series of standards for current and voltage sensors or detectors for fault path indication: Fault Path Indication
It can be achieved by appropriate equipment or functions, and can be divided into two categories according to their performance: one is the fault path indicator (FPI), and the other is the fault path indicator (FPI):
The class is the power distribution unit (DSU):
Different regions of the world have different names for fault path indicators, which also depend on their ability to detect different types of faults:
E:g:
--- Fault detector;
---Intelligent sensor;
--- Fault circuit indicator (FCI);
--- Short circuit indicator (SCI);
--- Earth Fault Indicator (EFI);
--- Test point fault circuit indicator;
---Comprehensive fault indicator:
A simpler version that uses only local information/signaling and/or local communication for fault path indication is called FPI, a more advanced version
Known as DSU: The latter is based on IEC 60870-5 and IEC 61850 communication protocols and is designed for smart grids: compared to transformers
In other words, digital communication technology will continue to change with future development needs:
Since such devices are not yet widely used in the industry, in-depth experience on the deep integration of electronic equipment and transformers needs to be further developed:
Accumulate on a broad basis:
In addition to the basic functions of FPI, DSU can optionally integrate other auxiliary functions, such as:
--- Voltage with/without detection function for medium voltage network automation, regardless of the presence of distributed energy sources [not used for fault confirmation (according to the
fault detection method used, fault acknowledgment can be used as a basic FPI function), nor is it used for safety protection covered by IEC 61243-5:
All relevant aspects];
---In various practical applications (such as: medium voltage grid automation, monitoring power flow, etc:), measuring voltage, current, active power, reactive power
power, etc:;
--- Manage the smart grid with suitable interfaces (e:g: voltage control and undesired
island operation);
--- Output the collected information in situ through a suitable interface;
--- Remote transmission of collected information;
---other:
A general FPI schematic is shown in Figure 1: DSUs usually have a more complex structure:
Index number description:
A---current sensor (there is also a voltage sensor if necessary), monitoring single-phase or three-phase;
B---Signal transmission between sensor and electronic unit;
C---In-place indicators (indicators, LEDs, markers, etc:);
D---Analog, digital and/or communication input/output for remote signaling/remote control (hard wired and/or wireless);
E---Connect with the field device;
F---Signal conditioning and indicating unit;
G---Power supply:
Current sensors can detect fault current paths without any circuit connection to each phase (eg: feed-through current sensors, magnetic field sensors):
FPI does not have to have all of the above functions, it depends on its own complexity and technology: But at least one of the functions in C or D:
Figure 1 General structure of FPI
0:2 Relationship of this document to the IEC 61850 series
IEC 61850 is a set of international standards for communications and systems supporting power automation:
The GB/T 41135 series of standards also introduces a set of special namespaces to support the integration of FPI/DSU and power automation:
In addition, this series of standards also defines appropriate data models and different communication interface profiles to support different applications of FPI/DSU
Scenes:
For the most complex versions of FPIs (eg: DSUs commonly used in smart grids), some application scenarios rely on extended substation's
concept, this extended substation concept is used to realize intelligent electronic devices (IEDs) distributed on medium voltage feeders and located in the main substation:
Between intelligent electronic devices (IEDs), IEC 61850 is used for communication: This configuration mode will not be restricted to FPI/DSU devices, but will
Contains the characteristics required for the sub-substations where the main substation extends to the outgoing lines:
Fault path indication with current and voltage sensors or
Detectors Part 2: System Applications
1 Scope
This document describes electrical phenomena and power system responses during faults according to the most widely used distribution system architectures and fault topologies,
This defines the functionality of the Fault Path Indicator (FPI) and the Power Distribution Unit (DSU) (including current and/or voltage sensors for the FPI, DSU)
sexual requirements: FPI and DSU are a single device or a combination of multiple devices/functions that can be used to detect faults and indicate the location of the fault:
This document is intended to guide the user according to the adopted scheme and operating rules (which are customary, and/or depend on national statutes to provide
Constraints on electrical continuity and power quality), selecting the appropriate
FPI/DSU and proper operating scheme:
Note 1: Fault location refers to the location relative to the FPI/DSU installation point in the grid (upstream or downstream of the FPI/DSU location) or the fault current through the FPI/DSU
Orientation of DSU: Considering the characteristics and operating conditions of the power system with the FPI/DSU installed, the fault location can be:
--- Derived directly from the FPI/DSU, or;
---From a centralized system that uses more FPI or DSU information:
Note 2: This document mainly focuses on the system response during the fault, which is classified by the FPI/DSU fault detection capability level described in GB/T 41135:1
"Core basis", all the requirements in GB/T 41135:1 are specified in detail:
2 Normative references
The contents of the following documents constitute essential provisions of this document through normative references in the text: Among them, dated citations
documents, only the version corresponding to that date applies to this document; for undated references, the latest edition (including all amendments) applies to
this document:
GB/T 41135:1 Current and voltage sensors or detectors for fault path indication - Part 1: General principles and requirements
(GB/T 41135:1-2021,IEC 62689-1:2016,MOD)
3 Terms and Definitions
The terms and definitions defined in GB/T 41135:1 and the following apply to this document:
3:1 Terms and Definitions Related to Neutral Grounding
3:1:1
arc-suppression coil
It is connected between the neutral point and the ground of the power system to compensate for the phase-to-ground capacitive current in the case of a single-phase ground fault (resonance-ground system):
Reactor:
NOTE: In order to make ground fault detection and/or fault removal easier, a pure reactor with a high quality factor Q is usually used instead of a resistive-reactive impedance:
[Source: GB/T 2900:95-2015, 3:4:10]
3:2 Abbreviations and symbols
Abbreviations and symbols defined in GB/T 41135:1 apply to this document:
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — all pages — is available in the English PDF.
Referenced standards
Normative references
GB/T 41135 · IEC 62689
How to Buy GB/T 41135.2-2021
- 1Add to cart. Click the "Buy GB/T 41135.2-2021" button on this page. You can add more standards before checkout.
- 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
- 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 41135.1-2021 — Current and voltage sensors or detectors, to be used for fault passage indication purposes - Part 1: General principles and requirements
GB/T 46830.2-2026 — Plastics - Liquid crystal polymer (LCP) moulding and extrusion materials - Part 2: Preparation of test specimens and determination of properties
GB/T 28593-2026 — Sand and dust weather warning levels
Secure payment via Stripe
Payments accepted
GB/T 41135.2-2021
$665.00