GB/T 41135.2-2021Current and voltage sensors or detectors, to be used for fault passage indication purposes - Part 2: System aspects (English PDF)

Also coversGBT41135.2-2021

Open the GB/T 41135.2-2021 preview as PDF

Preview — first pages of GB/T 41135.2-2021

This is a limited preview

Buy now to download the full PDF

Issued by

State Administration for Market Regulation, China National Standardization Administration

Level / Type

National · Recommended

Issue date

December 31, 2021

Implementation date

July 1, 2022

Scope

GB/T 41135.2-2021 (Current and voltage sensors or detectors, to be used for fault passage indication purposes - Part 2: System aspects) is available as an English-translated PDF.

GB/T 41135.2-2021 — This document describes electrical phenomena and power system responses during faults according to the most widely used distribution system architectures and fault topologies, This defines the functionality of the Fault Path Indicator (FPI) and the Power Distribution Unit (DSU) (including current and/or voltage sensors for the FPI, DSU) sexual requirements: FPI and DSU are a single device or a combination of multiple devices/functions that can be used to detect faults and indicate the location of the fault: This document is intended to guide the user according to the adopted scheme and operating rules (which are customary, and/or depend on national statutes to provide Constraints on electrical continuity and power quality), selecting the appropriate FPI/DSU and proper operating scheme: Note 1: Fault location refers to the location relative to the FPI/DSU installation point in the grid (upstream or downstream of the FPI/DSU location) or the fault current through the FPI/DSU Orientation of DSU: Considering the characteristics and operating conditions of the power system with the FPI/DSU installed, the fault location can be: --- Derived directly from the FPI/DSU, or; ---From a centralized system that uses more FPI or DSU information: Note 2: This document mainly focuses on the system response during the fault, which is classified by the FPI/DSU fault detection capability level described in GB/T 41135:1 "Core basis", all the requirements in GB/T 41135:1 are specified in detail:

Document preview — GB/T 41135.2-2021

National Standard of the People's Republic of China

Classification
K 41

Issued by: State Administration for Market Regulation, China National Standardization Administration

Contents

  • foreword
  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and Definitions

foreword

This document is in accordance with the provisions of GB/T 1:1-2020 "Guidelines for Standardization Work Part 1: Structure and Drafting Rules of Standardization Documents"

drafted:

This document is Part 2 of GB/T 41135 "Current and Voltage Sensors or Detectors for Fault Path Indication": GB/T 41135

The following sections have been published:

--- Part 1: General principles and requirements;

--- Part 2: System applications:

This document uses the redrafted method to modify the use of IEC 62689-2:2016 "Current and voltage sensors or detectors for fault path indication

Part 2: System Applications":

The technical differences between this document and IEC 62689-2:2016 and their reasons are as follows:

--- In order to adapt to my country's national conditions, the normative references in Chapter 2 are replaced by GB/T 41135:1, which has been modified and adopted international standards:

IEC 62689-1:

The following editorial changes have also been made to this document:

--- The scope has been rewritten;

--- In order to adapt to my country's national conditions, the content of Note 2 in 3:1:1 has been deleted;

--- Correct the error in the IEC standard, in paragraph 1 of 5:2:3:4 (5:2:5 in this document), change "see 5:2:4" to "see 5:2:4"

Figure 3"; in paragraph 1 of 5:2:4:2 (5:2:6:2 in this document), delete "Figure 21"; in Figure A:4 and formula (A:13), use

"I

2,rsd" replaces "I" in the IEC standard

2,0"; in paragraph 9 of B:1, use "A2(FPI/DSU 2)" and "A3(FPI/

DSU 3)" replaces "A3 (FPI/DSU 3)" and "A4 (FPI/DSU 4)" in the IEC standard, respectively:

In the latter paragraph, replace "FPI/DSU (A1 or A2)" in the IEC standard with "FPI/DSU (A2 or A3)";

--- Adjust 5:2:3:3 and 5:2:3:4 of the IEC standard to 5:2:4 and 5:2:5 respectively, and the numbers of other clauses shall be extended in turn;

---Improved the symbols and descriptions of some electrical graphics;

--- The formulas in Appendix A are numbered uniformly;

--- References have been adjusted:

Please note that some content of this document may be patented: The issuing agency of this document assumes no responsibility for identifying patents:

Introduction

0:1 Overview

GB/T 41135 is a series of standards for current and voltage sensors or detectors for fault path indication: Fault Path Indication

It can be achieved by appropriate equipment or functions, and can be divided into two categories according to their performance: one is the fault path indicator (FPI), and the other is the fault path indicator (FPI):

The class is the power distribution unit (DSU):

Different regions of the world have different names for fault path indicators, which also depend on their ability to detect different types of faults:

E:g:

--- Fault detector;

---Intelligent sensor;

--- Fault circuit indicator (FCI);

--- Short circuit indicator (SCI);

--- Earth Fault Indicator (EFI);

--- Test point fault circuit indicator;

---Comprehensive fault indicator:

A simpler version that uses only local information/signaling and/or local communication for fault path indication is called FPI, a more advanced version

Known as DSU: The latter is based on IEC 60870-5 and IEC 61850 communication protocols and is designed for smart grids: compared to transformers

In other words, digital communication technology will continue to change with future development needs:

Since such devices are not yet widely used in the industry, in-depth experience on the deep integration of electronic equipment and transformers needs to be further developed:

Accumulate on a broad basis:

In addition to the basic functions of FPI, DSU can optionally integrate other auxiliary functions, such as:

--- Voltage with/without detection function for medium voltage network automation, regardless of the presence of distributed energy sources [not used for fault confirmation (according to the

fault detection method used, fault acknowledgment can be used as a basic FPI function), nor is it used for safety protection covered by IEC 61243-5:

All relevant aspects];

---In various practical applications (such as: medium voltage grid automation, monitoring power flow, etc:), measuring voltage, current, active power, reactive power

power, etc:;

--- Manage the smart grid with suitable interfaces (e:g: voltage control and undesired

island operation);

--- Output the collected information in situ through a suitable interface;

--- Remote transmission of collected information;

---other:

A general FPI schematic is shown in Figure 1: DSUs usually have a more complex structure:

Index number description:

A---current sensor (there is also a voltage sensor if necessary), monitoring single-phase or three-phase;

B---Signal transmission between sensor and electronic unit;

C---In-place indicators (indicators, LEDs, markers, etc:);

D---Analog, digital and/or communication input/output for remote signaling/remote control (hard wired and/or wireless);

E---Connect with the field device;

F---Signal conditioning and indicating unit;

G---Power supply:

Current sensors can detect fault current paths without any circuit connection to each phase (eg: feed-through current sensors, magnetic field sensors):

FPI does not have to have all of the above functions, it depends on its own complexity and technology: But at least one of the functions in C or D:

Figure 1 General structure of FPI

0:2 Relationship of this document to the IEC 61850 series

IEC 61850 is a set of international standards for communications and systems supporting power automation:

The GB/T 41135 series of standards also introduces a set of special namespaces to support the integration of FPI/DSU and power automation:

In addition, this series of standards also defines appropriate data models and different communication interface profiles to support different applications of FPI/DSU

Scenes:

For the most complex versions of FPIs (eg: DSUs commonly used in smart grids), some application scenarios rely on extended substation's

concept, this extended substation concept is used to realize intelligent electronic devices (IEDs) distributed on medium voltage feeders and located in the main substation:

Between intelligent electronic devices (IEDs), IEC 61850 is used for communication: This configuration mode will not be restricted to FPI/DSU devices, but will

Contains the characteristics required for the sub-substations where the main substation extends to the outgoing lines:

Fault path indication with current and voltage sensors or

Detectors Part 2: System Applications

1 Scope

This document describes electrical phenomena and power system responses during faults according to the most widely used distribution system architectures and fault topologies,

This defines the functionality of the Fault Path Indicator (FPI) and the Power Distribution Unit (DSU) (including current and/or voltage sensors for the FPI, DSU)

sexual requirements: FPI and DSU are a single device or a combination of multiple devices/functions that can be used to detect faults and indicate the location of the fault:

This document is intended to guide the user according to the adopted scheme and operating rules (which are customary, and/or depend on national statutes to provide

Constraints on electrical continuity and power quality), selecting the appropriate

FPI/DSU and proper operating scheme:

Note 1: Fault location refers to the location relative to the FPI/DSU installation point in the grid (upstream or downstream of the FPI/DSU location) or the fault current through the FPI/DSU

Orientation of DSU: Considering the characteristics and operating conditions of the power system with the FPI/DSU installed, the fault location can be:

--- Derived directly from the FPI/DSU, or;

---From a centralized system that uses more FPI or DSU information:

Note 2: This document mainly focuses on the system response during the fault, which is classified by the FPI/DSU fault detection capability level described in GB/T 41135:1

"Core basis", all the requirements in GB/T 41135:1 are specified in detail:

2 Normative references

The contents of the following documents constitute essential provisions of this document through normative references in the text: Among them, dated citations

documents, only the version corresponding to that date applies to this document; for undated references, the latest edition (including all amendments) applies to

this document:

GB/T 41135:1 Current and voltage sensors or detectors for fault path indication - Part 1: General principles and requirements

(GB/T 41135:1-2021,IEC 62689-1:2016,MOD)

3 Terms and Definitions

The terms and definitions defined in GB/T 41135:1 and the following apply to this document:

3:1 Terms and Definitions Related to Neutral Grounding

3:1:1

arc-suppression coil

It is connected between the neutral point and the ground of the power system to compensate for the phase-to-ground capacitive current in the case of a single-phase ground fault (resonance-ground system):

Reactor:

NOTE: In order to make ground fault detection and/or fault removal easier, a pure reactor with a high quality factor Q is usually used instead of a resistive-reactive impedance:

[Source: GB/T 2900:95-2015, 3:4:10]

3:2 Abbreviations and symbols

Abbreviations and symbols defined in GB/T 41135:1 apply to this document:

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — all pages — is available in the English PDF.

Referenced standards

Normative references

GB/T 41135 · IEC 62689

How to Buy GB/T 41135.2-2021

  1. 1Add to cart. Click the "Buy GB/T 41135.2-2021" button on this page. You can add more standards before checkout.
  2. 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
  3. 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
  4. 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 41135.2-2021

$665.00

$565.00for partners