GB/T 20840.102-2020Instrument transformers - Part 102: Ferroresonance oscillations in substations with inductive voltage transformers (English PDF)

Also coversGBT20840.102-2020

Open the GB/T 20840.102-2020 preview as PDF

Preview — first pages of GB/T 20840.102-2020

This is a limited preview

Buy now to download the full PDF

Issued by

State Administration for Market Regulation, China National Standardization Administration

Level / Type

National · Recommended

Issue date

March 31, 2020

Implementation date

October 1, 2020

Scope

GB/T 20840.102-2020 (Instrument transformers - Part 102: Ferroresonance oscillations in substations with inductive voltage transformers) is available as an English-translated PDF.

GB/T 20840.102-2020 — This part of GB/T 20840 gives the principles, examples, analysis and suppression of ferromagnetic resonance phenomena in substations with electromagnetic voltage transformers Introduction of manufacturing methods. Electromagnetic voltage transformers and other non-linear inductive components will cause ferromagnetic resonance, which will give electromagnetic voltage Transformers and other equipment cause great harm. This part is applicable to guide the calculation, simulation, experiment, measurement and prevention and suppression measures of ferromagnetic resonance in the power grid.

Document preview — GB/T 20840.102-2020

National Standard of the People's Republic of China

ICS
29.180
Classification
K 41

Issued by: State Administration for Market Regulation, China National Standardization Administration

Contents

  • Foreword
  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Overview of ferromagnetic resonance
  • 3.1 Basic principles

Foreword

GB/T 20840 "Transformer" is divided into the following parts.

--- Part 1. General technical requirements;

--- Part 2. Supplementary technical requirements for current transformers;

--- Part 3. Supplementary technical requirements for electromagnetic voltage transformers;

--- Part 4. Supplementary technical requirements for combined transformers;

--- Part 5. Supplementary technical requirements for capacitive voltage transformers;

--- Part 6. Supplementary general technical requirements for low power transformers;

--- Part 7. Electronic Voltage Transformer;

--- Part 8. Electronic Current Transformer;

--- Part 9. Digital Interface of Transformers;

--- Part 102. Ferromagnetic resonance in substations with electromagnetic voltage transformers;

--- Part 103. Application of transformers in power quality measurement.

This part is Part 102 of GB/T 20840.

This section was drafted in accordance with the rules given in GB/T 1.1-2009.

This part uses the redrafting method to modify and adopt IEC TR61869-102..2014 `` Transformers Part 102. With Electromagnetic Voltage

Ferromagnetic resonance in transformer substations. "

This part is structurally adjusted compared with IEC TR61869-102..2014. Appendix A lists this part and IEC TR61869-

A comparative list of 102,2014 chapter, article and figure numbers.

There are technical differences between this part and IEC TR61869-102..2014, and the terms involved in these differences have been adopted on the outside page

The vertical single line (|) at the margin is marked. Appendix B gives a list of corresponding technical differences and their causes.

This section also made the following editorial changes.

--- The serial number 6.3 mentioned in 9.3 is wrong, correct it to 7.3;

--- Change the two kinds of three-phase terminal signs "L1, L2, L3" and "R, S, T" in IEC TR61869-102..2014 to "A, B, C";

--- Change the neutral point-to-earth capacitor voltage symbol UC to UeC. ;

--- Change the neutral point voltage from "en" to "3U0";

--- Change the fractional expression with remainder to the fractional expression without remainder, such as "162/3Hz" to "50/3Hz";

--- Change the line cross-section icon in Figure 17 of IEC TR61869-102..2014 from colored fill to pattern fill (see Appendix C, Figure C.4);

--- Adjusted references and added IEC 61869-3 and IEC 61869-4;

--- Change the IEC standard cited in A.2 of IEC TR61869-102..2014 to the corresponding national standard (see D.2);

--- The primary and secondary terminal signs of the voltage transformers of IEC TR61869-102..2014 were changed to "A, N" and "a, n";

--- Change the primary and secondary terminal signs of current transformers of IEC TR61869-102..2014 from "K, L" and "k, l" to "P1, P2"

And "s1, s2".

This part is proposed by China Electrical Equipment Industry Association.

This part is under the jurisdiction of the National Transformer Standardization Technical Committee (SAC/TC222).

This section was drafted by. State Grid Shaanxi Electric Power Research Institute, Shenyang Transformer Research Institute Co., Ltd., China Power

Science Research Institute Co., Ltd., Yunnan Power Grid Co., Ltd. Electric Power Research Institute, TBEA Kangjia (Shenyang) Transformer Co., Ltd.

Company, Dalian First Transformer Co., Ltd., Dalian North Transformer Group Co., Ltd., Jiangsu Kexing Electric Co., Ltd., Zhejiang Skyrim

Transformer Co., Ltd., Jiangsu Jingjiang Transformer Co., Ltd., Chongqing Shancheng Electric Appliance Co., Ltd., Jiangxi Gandian Electric Co., Ltd.,

Lianhuayi Electric Appliance Co., Ltd., State Grid Jilin Electric Power Co., Ltd. Electric Power Research Institute, State Grid Jiangxi Electric Power Co., Ltd.

Research Institute, State Grid Shanghai Electric Power Company Electric Power Research Institute.

Introduction

Since the first half of the 20th century, many scholars have carried out research on the phenomenon of ferromagnetic resonance. R. Rüdenberg mainly studied fundamental harmonics

Vibration [1], other scholars have studied high frequency and crossover resonance. Afterwards K. Heuck and KDDettmann [2] made a detailed summary of this phenomenon

General introduction. Bergmann [3,4] conducted various basic ferromagnetic resonance experiments, and their research results are widely cited. GermayN.,

MasteroS. And VromanJ. Published related review articles at the 1974 CIGRE conference [5].

In the past 20 years, electromagnetic voltage transformers according to IEC 61869-3 and combined transformers of IEC 61869-4 have been

The problem of ferromagnetic resonance in the station has been discussed in the International Large Grid Working Group and the IEEE Committee in the United States. The results of the discussion were published in Dadian

Internet technical report [5] and IEEE publication [6].

The publication of these publications is due to the frequent occurrence of ferromagnetic resonance in the substation, so it is necessary to develop more efficient systems and equipment.

This development trend will lead to the following results.

a) The rated voltage Upr of the equipment is transferred to the highest voltage Um allowed by the equipment (IEC 60071-1 [7])

b) Increase the magnetic flux density B by reducing the iron core cross section of the electromagnetic voltage transformer;

c) By using new equipment (such as medium-voltage and high-voltage transformers) to reduce the capacitance of the substation and cause the excitation voltage of the non-linear circuit

improve;

d) Using digital instruments and relays with a load of about 1VA, the actual load of the substation is reduced, and the electromagnetic voltage mutual inductance

The device has always specified a higher secondary load (from 50VA to 400VA). However, in fact these high loads are usually not

Enough to cause ferromagnetic resonance.

Transformers. Part 102. With electromagnetic voltage

Ferromagnetic resonance in transformer substation

1 Scope

This part of GB/T 20840 gives the principles, examples, analysis and suppression of ferromagnetic resonance phenomena in substations with electromagnetic voltage transformers

Introduction of manufacturing methods. Electromagnetic voltage transformers and other non-linear inductive components will cause ferromagnetic resonance, which will give electromagnetic voltage

Transformers and other equipment cause great harm.

This part is applicable to guide the calculation, simulation, experiment, measurement and prevention and suppression measures of ferromagnetic resonance in the power grid.

2 Normative references

The following documents are essential for the application of this document. For dated references, only the dated version applies to this article

Pieces. For the cited documents without date, the latest version (including all amendments) applies to this document.

GB/T 20840.3-2013 Transformers Part 3. Supplementary technical requirements for electromagnetic voltage transformers (IEC 61869-3.

2011, MOD)

GB/T 20840.5 Transformers Part 5. Supplementary technical requirements for capacitive voltage transformers (GB/T 20840.5-2013,

IEC 61869-5..2011, MOD)

3 Overview of ferromagnetic resonance

3.1 Basic principles

Ferromagnetic resonance is a kind of non-linear oscillation, which is switched on and off in a system consisting of an inductive element with a core, a capacitor and an AC voltage source

It may occur during load and line failure.

Iron core saturation is the main cause of ferromagnetic resonance. If the magnetic flux density of the electromagnetic voltage transformer exceeds its saturation magnetic flux density

B -> S, the magnetic field strength H -> eff and the magnetic flux density B will have a non-linear relationship, as shown in Figure 1, its inductive reactance B ^

A sharp decrease, which lifts the generation of ferromagnetic resonance

To be effective.

Ferromagnetic resonance generally occurs in high and medium voltage substations or other local power grids. For example. when the high-voltage winding of an electromagnetic voltage transformer is

When the capacitor is connected in series to an AC voltage source system, single-phase ferromagnetic resonance may occur, as shown in Figure 2, when the neutral point of the low voltage side of the transformer is not connected

When grounded, three-phase ferromagnetic resonance may occur.

The above is the basic situation of ferromagnetic resonance. Ferromagnetic resonance can also occur in complex power grids.

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — all pages — is available in the English PDF.

Referenced standards

Normative references

GB/T 20840.3-2013 · IEC 61869 · GB/T 20840.5 · GB/T 20840.5-2013

How to Buy GB/T 20840.102-2020

  1. 1Add to cart. Click the "Buy GB/T 20840.102-2020" button on this page. You can add more standards before checkout.
  2. 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
  3. 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
  4. 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB/T 20840.102-2020

$680.00

$580.00for partners