Scope

GB 50877-2014 is the English-translated version of 防火卷帘防火门防火窗施工及收规范.

GB 50877-2014 — 1.0.1 This code is formulated in order to the quality and service function during the installation of fire resistant shutters, fire resistant doorsets and fire resistant windows, reduce fire hazards and protect personal and property safety.

Found what you need?

Document preview — GB 50877-2014

National Standard of the People's Republic of China

Issued by: Ministry of Housing and Urban-Rural Development;

Contents

  • 1 General Provisions
  • 2 Terms
  • 3 Basic Requirement
  • 4 Inspection
  • 4.1 General Requirement
  • 4.2 Fire Resistant Shutters Inspection
  • 4.3 Fire Resistant Doorsets Inspection
  • 4.4 Fire Resistant Windows Inspection
  • 5 Installation
  • 5.1 General Requirement
  • 5.2 Fire Resistant Shutters Installation
  • 5.3 Fire Resistant Doorsets Installation
  • 5.4 Fire Resistant Windows Installation
  • 6 Commissioning
  • 6.1 General Requirement
  • 6.2 Fire Resistant Shutters Commissioning
  • 6.3 Fire Resistant Doorsets Commissioning
  • 6.4 Fire Resistant Windows Commissioning
  • 7 Acceptance Test
  • 7.1 General Requirement
  • 7.2 Fire Resistant Shutters Acceptance
  • 7.3 Fire Resistant Doorsets Acceptance
  • 7.4 Fire Resistant Windows Acceptance
  • 8 Maintenance and Management
  • Appendix A -- Inspection Records for Quality Management of Construction Site

1 General Provisions

1.0.1 This code is formulated in order to the quality and service function during the installation of fire resistant shutters, fire resistant doorsets and fire resistant windows, reduce fire hazards and protect personal and property safety.

1.0.2 This code is applicable to the installation, acceptance and maintenance

management of fire resistant shutters, fire resistant doorsets and fire resistant windows for construction, extension and renovation.

1.0.3 The requirements for installation and acceptance specified in relevant engineering documents and contracts for installing and acceptance of fire resistant shutters, fire resistant doorsets and fire resistant windows shall at least meet those specified in this code.

1.0.4 Installation, acceptance and maintenance management of fire resistant

shutters, fire resistant doorsets and fire resistant windows shall not only meet the requirements stipulated in this code, but also comply with those specified in the current relevant national standards.

2 Terms

2.0.1 Fire resistant shutter

A kind of facility with its frame to be capable of fire prevention and thermal insulation in a certain period of time.

2.0.2 Steel fire resistant shutter

A kind of facility, equipped with door roller and control box, whose slat, guide rail, riser plate, lintel and box are made of steel materials.

2.0.3 Mineral fiber composites fire resistant shutter

A kind of facility, equipped with door roller and control box, whose shutter surface (equipped with stainless steel wire or rope) is made of mineral fibers, clamp plate, guide rail, riser plate, lintel and box are of steel materials.

3 Basic Requirement

3.0.1 Corresponding technical standard for installation, process specification and implementation scheme, quality management system, installation quality control and inspection system shall be available for management of construction site. The quality control on construction site shall be inspected and recorded in accordance with the requirements of Appendix A.

3.0.2 Prior to installation of fire resistant shutters, fire resistant doorsets and fire

resistant windows, the following technical information shall be available.

3.0.4 Subsection project, sub-subsection project and sub-item project relating to fire

resistant shutters, fire resistant doorsets and fire resistant windows may be categorized in accordance with Appendix B of this code.

3.0.5 Installation quality control and acceptance of fire resistant shutters, fire

resistant doorsets and fire resistant windows shall be performed in accordance with the requirements of Chapter 4~Chapter 7.

3.0.6 Qualification judgment of inspection and acceptance shall meet the following

requirements.

4 Inspection

4.1 General Requirement

4.1.1 Site inspection held by installation organization and supervised by supervision organization shall be performed for main parts and accessories of fire resistant shutters, fire resistant doorsets and fire resistant windows.

4.2 Fire Resistant Shutters Inspection

4.2.1 Fire resistant shutter and its corresponding smoke and heat detectors

shall be provided with delivery certificate and valid documentation conforming to the requirements of market-access system. Its model/specification and fire resistance shall meet the design requirements.

4.2.2 Permanent labels shall be installed obviously on each set of fire resistant

shutter and its corresponding door roller, controller, manual button box and thermal release device., on which the name and model/specification, fire resistance and trademark of product, as well as name and address of production unit (manufacturer), delivery date, product No. or production batch No., and executive standard shall be marked.

4.3 Fire Resistant Doorsets Inspection

4.3.1 Fire resistant doorset shall be provided with delivery certificate and valid

documentation conforming to the requirements of market-access system. Its model/specification and fire resistance shall meet the design requirements.

Inspection quantity. 100% inspection.

Inspection method. inspecting whether name, model/specification and fire resistance of the product meet the valid documentation conforming to the requirements of market-access system and design requirements.

4.4 Fire Resistant Windows Inspection

4.4.1 Fire resistant window shall be provided with delivery certificate and valid

documentation conforming to the requirements of market-access system. Its model/specification and fire resistance shall meet the design requirements.

Inspection quantity. 100% inspection.

Inspection method. inspecting whether name, model/specification and fire resistance of the product meet the valid documentation conforming to the requirements of market-access system and design requirements.

4.4.2 Permanent label shall be installed obviously on each set of fire resistant

windows, on which the name and model/specification, fire resistance and trademark of product, as well as the name and address of production unit (manufacturer), delivery date, product No. or production batch No., and executive standard shall be marked.

5 Installation

5.1 General Requirement

5.1.1 Fire resistant shutters, fire resistant doorsets and fire resistant windows shall

be installed in accordance with the requirements of installation drawing, design instructions, design alteration notice and other technical documents.

5.2 Fire Resistant Shutters Installation

5.2.1 Fire resistant shutter surface and slat shall be installed according to the following requirements.

5.2.2 Guide rail shall be installed according to the following requirements.

1 Embedded depth of guide rail into fire resistant shutter slat or surface shall be in accordance with Table 5.2.2.

5.2.7 Protective cover (box) shall be installed according to the following

requirements.

5.2.8 Installation position of thermal release device shall meet the requirements of design and product instructions.

5.3 Fire Resistant Doorsets Installation

5.3.1 Fire resistant doorset shall be opened towards evacuation direction and shall

be manually opened from any side after shutdown, except special circumstances.

5.3.2 Normally-closed fire resistant doorset shall be equipped with door closer, etc.;

double-leave and multi-leave fire resistant doorsets shall be equipped with sequencer.

5.3.8 Cement mortar shall be filled in the door frame of steel fire resistant doorset.

Door frame and wall shall be firmly connected with embedded steel or expansion bolt etc., and spacing between fixed points should not be greater than 600 mm.

5.3.9 Lapping dimension between door leaf and door frame of fire resistant doorset

shall not be less than 12mm.

5.3.10 Matching free gap between door leaf and door frame of fire resistant doorset

shall meet the following requirements.

5.4.4 Automatic controlled fire window shall be equipped with thermal release

device which has control over automatically closing window sash according to the requirements of design and product instructions in case of fire.

6 Commissioning

6.1 General Requirement

6.1.1 Commissioning shall be carried out after installation of fire resistant shutters, fire resistant doorsets and fire resistant windows; if there is fire alarm system, commissioning shall be carried out after commissioning of relevant fire alarm system and linkage control equipment is qualified, which is in the charge of installation organization and under the supervision of supervision organization.

6.1.3 For commissioning of fire resistant shutters, fire resistant doorsets and fire resistant windows, inspection record about commissioning process shall be filled in according to Table C.0.1-4 in Appendix C of this code. Construction organization shall apply for acceptance to installation organization after commissioning is qualified.

6.2 Fire Resistant Shutters Commissioning

6.2.1 Commissioning shall be carried out for energization, standby power supply, fire alarm, fault alarm, automatic control, manual control and dead-weight dropping of controller of fire resistant shutter, and the following requirements shall be met.

6.2.3 Operation commissioning of fire resistant shutter shall meet the following

requirements.

6.3 Fire Resistant Doorsets Commissioning

6.3.1 Normally-closed fire resistant doorsets shall close automatically when they are opened manually from any side. If signal feedback device is installed, it shall feedback on/off status to the fire control room.

6.3.2 Normally-open fire resistant doorsets shall close automatically after fire

detector on any side alarms, and shall feedback off signal to the fire control room.

Inspection quantity. 100% inspection.

6.3.3 Normally-open fire resistant doorsets shall close automatically after receiving

the out code sent manually by fire control room, and shall feedback the off signal to the fire control room.

6.4.3 The automatic controlled fire window shall close automatically as soon as receiving the out code sent by the fire control room, and the shutoff signal shall be fed back to the fire control room.

6.4.4 As soon as the thermal release device installed at the automatic controlled fire window takes operation, the automatic controlled fire window shall close automatically within 60s.

7 Acceptance Test

7.1 General Requirement

7.1.1 After fire resistant shutters, fire resistant doorsets and fire resistant

windows have been commissioned, acceptance of project quality shall be performed on the basis of qualified assessment of self-inspection by the installation organization.

7.1.2 Before acceptance of project quality of fire resistant shutters, fire resistant

doorsets and fire resistant windows, the installation organization shall provide the following document information and fill in the information verification record according to D.0.1-1 in Appendix D of this code.

7.2 Fire Resistant Shutters Acceptance

7.2.1 Model, specification and quantity of fire resistant shutter, as well as installation

position, etc., shall meet the design requirements.

Inspection quantity. 100% inspection.

Inspection method. visual inspection.

7.2.2 The quality acceptance of construction and installation of fire resistant shutter shall meet those specified in 5.2 of this code.

7.2.3 The system function acceptance of fire resistant shutter shall meet those specified in 6.2 of this code.

7.3 Fire Resistant Doorsets Acceptance

7.3.1 Model, specification and quantity of fire resistant doorset, as well as installation position, etc., shall meet the design requirements.

Inspection quantity. 100% inspection.

7.4 Fire Resistant Windows Acceptance

7.4.1 Model, specification and quantity of fire resistant window, as well as installation

position, etc., shall meet the design requirements.

7.4.2 Installation quality acceptance of fire resistant window shall meet those

specified in 5.4 of this code.

8 Maintenance and Management

8.0.1 Before fire resistant shutters, fire resistant doorsets and fire resistant windows

are put into service, the following document information shall be available.

8.0.2 The service organization shall be equipped with special personnel, who are specially trained and qualified for fire control, to take the responsibility of regular inspection and maintenance management of fire resistant shutters, fire resistant doorsets and fire resistant windows.

8.0.6 The following functions of fire resistant shutter, fire resistant doorset and automatic controlled fire window shall be inspected once a quarter.

1 Manually startup the controller at both inner and outer sides of fire resistant

8.0.7 The following functions of fire resistant shutter, fire resistant doorset and automatic controlled fire window shall be inspected once a year.

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 47 pages — is available in the English PDF.

Referenced standards

How to Download GB 50877-2014

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
47 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB 50877-2014

$345.00