Valid

GB 50193-1993Code of design for carbon dioxide fire extinguishing systems (English PDF)

Preview PDF

This is a limited preview

Buy now to download the full PDF (49 pages)

Need quotation for your management?

Get a formal quotation for GB 50193-1993 in 30 minutes.

Issued by

Jointly Issued by Ministry of Housing and Urban-Rural Construction of the People's, General Administration of Quality Supervision, Inspection and, issued by the Ministry of Housing and Urban-Rural Development.

Level / Type

National · Mandatory

Issue date

December 21, 1993

Implementation date

August 1, 1994

Scope

GB 50193-1993 (Code of design for carbon dioxide fire extinguishing systems) is available as an English-translated PDF.

GB 50193-1993 — This standard applies to: new construction, renovation, expansion project and the production and storage of carbon dioxide extinguishing system set design.

Found what you need?

Document preview — GB 50193-1993

National Standard of the People's Republic of China

ICS
13.220.10
Classification
P 16

Issued by: Jointly Issued by Ministry of Housing and Urban-Rural Construction of the People's, General Administration of Quality Supervision, Inspection and, issued by the Ministry of Housing and Urban-Rural Development.

Contents

  • General Provision
  • 2 Term and Symbol
  • 2.1 Term
  • 2.2 Symbol
  • 3 System Design
  • 3 .1 General Requirement
  • 3.2 Total Flooding Extinguishing System
  • 3 .3 Total Flooding Extinguishing System
  • 4 Pipe Network Calculations
  • 5 System Component
  • 5. I Storage System
  • 5 .2 Selector Valve and Nozzle
  • 5.3 Pipe and Accessory
  • 6 Control and Operation
  • 7 Safety Requirements
  • Appendix A Material Factor, Design Concentration and Inhibition Time
  • Appendix B Equivalent Length of Pipe Accessories
  • Appendix C Pipe Pressure Sink
  • Appendix D YValue and Z Value of Carbon Dioxide
  • Appendix E Elevation Correction Factor
  • Appendix F Nozzle Inlet Pressure and Unit Area Injection Rate
  • Appendix G Explanation of Wording in This Code
  • Appendix H Nozzle Equivalent Orifice Dimension
  • Appendix J Specifications of Carbon Dioxide Fire Extinguishing System Pipes
  • 1 General Provision
  • 1.0.1 This code is formulated with a view to reasonably designing carbon dioxide extinguishing

2 Because the products and accessories made by different manufacturers are diverse from each

other in hydraulic equivalent loss length, the equivalent lengths of pipe accessories, determined according to the requirements of Appendix B in This code will be greatly different from the ones in practical situation;

3 The standard has not specified that mechanical air exhaust devices shall be arranged between storage containers, so leaks may be serious threat to the lives of staff in the rooms and rooms nearby;

4 The specific requirements are proposed in the shunt design of carbon dioxide gas transfer lined, for improving the pressure equalization of the pipe network.

The articles underline in This code are ones revised.

Chief drafting organization. Tianjin Fire Research Institute of Ministry of Public Security Participating organization. National Engineering research Center for fire Protection China National Center for Quality Supervision and Test of Fixed Fire-fighting Systems and Fire-resisting Building Components Nanjing Fire Protection Technology Co., Ltd.

Contents

General Provision ... 1

2 Term and Symbol ... 2

2.1 Term ... 2

2.2 Symbol ... 3

3 System Design ... 6 3 .1 General Requirement ... 6

3.2 Total Flooding Extinguishing System ... 7 3 .3 Total Flooding Extinguishing System ... 8

4 Pipe Network Calculations ... 11

5 System Component ... 14 5. I Storage System ... 14 5 .2 Selector Valve and Nozzle ... 15

5.3 Pipe and Accessory ... 15

6 Control and Operation ... 17

7 Safety Requirements ... 18 Appendix A Material Factor, Design Concentration and Inhibition Time ... 19 Appendix B Equivalent Length of Pipe Accessories ... 21 Appendix C Pipe Pressure Sink ... 22 Appendix D YValue and Z Value of Carbon Dioxide ... 23 Appendix E Elevation Correction Factor ... 24 Appendix F Nozzle Inlet Pressure and Unit Area Injection Rate ... 25 Appendix G Explanation of Wording in This Code ... 26 Appendix H Nozzle Equivalent Orifice Dimension ... 27 Appendix J Specifications of Carbon Dioxide Fire Extinguishing System Pipes ... 28

1 General Provision

1.0.1 This code is formulated with a view to reasonably designing carbon dioxide extinguishing system, reducing fire hazards, and protecting and the safety of people and property.

1.0.2 This code is applicable to the designs of carbon dioxide extinguishing systems arranged in new, rebuild and extended engineering and storage systems.

1.0.3 The design of carbon dioxide extinguishing system shall actively adopt new technique, process and equipment, and be of safety and application, state-of-the-art, and economic feasibility.

1.0.4 Carbon dioxide extinguishing systems may be used for extinguishing the following fires.

1.0.4.1 Gas fire, which the gad source can be Cutting off before fire extinction.

1.0.4.2 Liquid fire or meltable solid (like paraffin and asphalt) fire.

1.0.4.3 Solid surface fire and solid deep-seated fire (like cotton wool, fabric and paper).

1.0.4.4 Electric fire .

1.0.5 Carbon dioxide extinguishing systems must not be used for extinguishing the following fires.

1.0.5.1 Fires of chemicals (like nitrocellulose and blasting powder) containing oxidants.

1.0.5.2 Fires of active metals like kalium, sodium, magnesium, titanium and zirconium.

1.0.5.3 Fires of metal hydrides like potassium hydride and sodium hydride.

1.0.SA Total flooding carbon dioxide extinguishing system shall not be applied at the places where staffs stay often.

1.0.6 The design of carbon dioxide extinguishing system, besides the requirements of this code, shall also meet the requirements of the current related national standards.

2 Term and Symbol

2.1 Term

2.1.1 Total flooding extinguishing system

Fire extinguishing system which can eject carbon dioxide of finite concentration into a protected area within a specified time, and fully fill the whole protected area with carbon dioxide.

2.1.2 Local application extinguishing system

Fire extinguishing system which directly ejects carbon dioxide onto protected object at the design ejection rate; and lasts for a certain time.

2.1.3 Protected area

Close space meeting the application conditions of a total flooding carbon dioxide extinguishing system; and protected by the system.

2.1.4 Combined distribution systems

Fire extinguishing system in which a suit of carbon dioxide storage device is used to protect two or more protected areas/protected objects.

2.1.5 Flame extinguishing concentration

Minimum volume percentage (in a mixture of air and carbon dioxide) of carbon dioxide required to extinguish a certain fire, under the atmosphere 101 kPa and at the specified temperature.

2.1.6 Inhibition time

Time to keep the designed carbon dioxide concentration and extinguish solid deep-seated fire fully.

2.1.7 Pressure relief opening

An opening arranged on the exterior wall or top of a protected area to discharge internal super pressure of the protected area.

2.1.8 Equivalent orifice area

Converted orifice area of a standard nozzle with the water flow rate coefficient of 0.98.

2.1.9 Filling factor

Ratio of the mass of carbon dioxide stored in high pressure system container and the container volume.

2.1.9A Loading factor Ratio of the mass of liquid carbon dioxide stored in low-pressure system container and the container volume.

2.1.10 Material factor

Reduction coefficient of the design carbon dioxide concentration of combustible substance corresponding to 34% carbon dioxide concentration.

Vv--Volume of a protected area;

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 49 pages — is available in the English PDF.

Referenced standards

How to Download GB 50193-1993

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
49 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

GB 50193-1993

$60.00