NB/T 11513-2024Technical code for design of high altitude substation (English PDF)

高海拔变电站设计技术规程

Open the NB/T 11513-2024 preview as PDF

Preview — first pages of NB/T 11513-2024 (full document: 75 pages)

This is a limited preview

Buy now to download the full PDF (75 pages)

Issued by

NEA

Level / Type

Industry · Recommended

Issue date

May 24, 2024

Implementation date

November 24, 2024

Scope

NB/T 11513-2024 is the English-translated version of 高海拔变电站设计技术规程.

NB/T 11513-2024 is the Chinese technical code for designing substations at altitudes between 2 000 m and 5 000 m, from 110 kV up to 750 kV. It exists because thin air is a poor insulator and a poor coolant, and above about two kilometres every assumption built into ordinary substation design starts to drift. Air at 4 000 m has roughly 60 percent of the density it has at sea level, so a clearance that holds off a surge at sea level flashes over up high, the corona inception voltage falls and conductors that were quiet begin to hiss and to interfere with radio, transformers shed heat less effectively and have to be derated, and batteries, uninterruptible supplies and diesel generators all lose capacity. The Tibetan plateau adds everything else at once: high seismic intensity, extreme cold, fierce ultraviolet, wind-blown sand, and the highest thunderstorm day counts in the country. This code is what an engineer works from when all of that applies together. It sets the site selection rules, including the protected areas that must be avoided and the treatment of karst ground and seismogenic faults. The electrical part covers the choice of equipment against the combined environment rather than against altitude alone: three-phase transformers up to 330 kV and single-phase above, cooling selected for the real site conditions, temperature rise corrected for altitude under GB 1094.2, low pour point insulating oil below minus 25 degrees, heated or gas-mixture switchgear where the cold would liquefy SF6, ageing-resistant and sand-proof seals, and derated batteries, UPS and diesel sets. For conductors and hardware it fixes the current carrying correction below 4 000 m and requires test above it, and caps the maximum working field strength at 85 percent of the corona inception field strength for both conductors and fittings. The civil part covers architecture and structure, HVAC, water, drainage and fire protection, and - the section that has no counterpart in a lowland code - the oxygen enriched system that makes the control building habitable for the people who work in it. Environmental protection and soil and water conservation, and labour safety and occupational health, close the document, and two appendices give the measured flashover voltages for extra-high-voltage clearances and the required oxygen concentrations. It was issued on 24 May 2024 by the National Energy Administration and took effect on 24 November 2024.

Document preview — NB/T 11513-2024

National Standard of the People's Republic of China

ICS
29.240
Classification
P 62

Issued by: National Energy Administration of the PRC

Contents

  • Foreword2
  • 1 General provisions1
  • 2 Terms2
  • 3 Selection of the substation location3
  • 4 Electrical part5
  • 4.1 General requirements5
  • 4.2 Selection of electrical equipment5
  • 4.3 Selection of conductors and hardware6
  • 4.4 Overvoltage and insulation coordination7
  • 4.5 Electrical installation7
  • 5 Civil part9
  • 5.1 General requirements9
  • 5.2 Architecture and structure9
  • 5.3 Heating, ventilation and air conditioning11
  • 5.4 Water supply, drainage and fire protection12
  • 5.5 Oxygen enriched system12
  • 6 Environment protection, soil and water conservation14
  • 7 Labour safety and occupational health15
  • 7.1 General requirements15
  • 7.2 Labour safety15
  • 7.3 Occupational health16
  • Appendix A Flashover voltage test results for clearances of extra voltage substations18
  • Appendix B Requirements of oxygen concentration20

Foreword

This document was issued on 24 May 2024 by the National Energy Administration of the PRC and takes effect on 24 November 2024.

It is a NB/T standard: recommended rather than compulsory, but it is the text a Chinese reviewer applies when assessing a submission.

It is classified under ICS 29.240, Chinese classification P 62.

This standard was prepared in accordance with the requirements of the plan of the National Energy Administration for the formulation and revision of industry standards in the energy field. The drafting group carried out extensive investigation and research, carefully summarised practical experience, and prepared this standard on the basis of wide consultation.

The main technical content of this standard is: general provisions; terms; selection of the substation location; the electrical part; the civil part; environmental protection and soil and water conservation; and labour safety and occupational health.

This standard is administered by the National Energy Administration, and the organizations named in it are responsible for the interpretation of the specific technical content.

1 Scope

NB/T 11513-2024 is the Chinese technical code for designing substations at altitudes between 2 000 m and 5 000 m, from 110 kV up to 750 kV. It exists because thin air is a poor insulator and a poor coolant, and above about two kilometres every assumption built into ordinary substation design starts to drift. Air at 4 000 m has roughly 60 percent of the density it has at sea level, so a clearance that holds off a surge at sea level flashes over up high, the corona inception voltage falls and conductors that were quiet begin to hiss and to interfere with radio, transformers shed heat less effectively and have to be derated, and batteries, uninterruptible supplies and diesel generators all lose capacity. The Tibetan plateau adds everything else at once: high seismic intensity, extreme cold, fierce ultraviolet, wind-blown sand, and the highest thunderstorm day counts in the country. This code is what an engineer works from when all of that applies together. It sets the site selection rules, including the protected areas that must be avoided and the treatment of karst ground and seismogenic faults. The electrical part covers the choice of equipment against the combined environment rather than against altitude alone: three-phase transformers up to 330 kV and single-phase above, cooling selected for the real site conditions, temperature rise corrected for altitude under GB 1094.2, low pour point insulating oil below minus 25 degrees, heated or gas-mixture switchgear where the cold would liquefy SF6, ageing-resistant and sand-proof seals, and derated batteries, UPS and diesel sets. For conductors and hardware it fixes the current carrying correction below 4 000 m and requires test above it, and caps the maximum working field strength at 85 percent of the corona inception field strength for both conductors and fittings. The civil part covers architecture and structure, HVAC, water, drainage and fire protection, and - the section that has no counterpart in a lowland code - the oxygen enriched system that makes the control building habitable for the people who work in it. Environmental protection and soil and water conservation, and labour safety and occupational health, close the document, and two appendices give the measured flashover voltages for extra-high-voltage clearances and the required oxygen concentrations. It was issued on 24 May 2024 by the National Energy Administration and took effect on 24 November 2024.

1.0.1 This standard is formulated in order to meet the needs of national and industry standardization work, to achieve the aim of unifying and standardising the technical principles for the design of substations in high altitude areas, and to make the design of substations in high altitude areas comply with the relevant national policies and regulations and meet the requirements of safety and reliability, technical advancement and applicability, economic reasonableness and energy saving and environmental protection.

1.0.2 This standard applies to the design of 110 kV to 750 kV substations at altitudes from 2 000 m to 5 000 m, and specifies principally the design content related to high altitude.

1.0.3 The design of a high altitude substation should adopt new technologies, new equipment, new materials and new processes that are ready for application, in the light of the characteristics of the project and of the environmental and meteorological conditions.

1.0.4 In addition to complying with this standard, the design of a high altitude substation shall also comply with the provisions of the relevant current national standards.

2 Terms

2.0.1 altitude correction factor

The factor by which the coordination withstand voltage is corrected in order to take account of the difference in insulation strength between the mean pressure corresponding to the altitude at which the equipment operates and the standard reference pressure.

2.0.2 supplying oxygen by diffusion system

The complete set of equipment that supplies oxygen to a room by diffusion, through pipework or through terminals.

3 Selection of the substation location

3.0.1 The selection of the substation location shall satisfy the requirements of the power system plan, of the urban or rural master plan, of the land use master plan and of environmental protection, and the best site option shall be determined by a comprehensive technical and economic comparison according to the conditions of transport, terrain and geology, flood control and drainage, water supply and drainage, and power supply.

3.0.2 The site shall avoid the following protected areas and areas where construction is restricted:

1 ecological red line protection areas and permanent basic farmland protection areas;

2 areas of restricted construction around national and provincial level important historical relics and monuments;

3 areas of restricted construction in national and provincial level scenic areas, natural ecological reserves, important water supply sources and soil and water conservation areas;

4 areas of restricted construction such as airport clearance zones and military installations;

5 areas of restricted construction around important astronomical, meteorological and seismic observation facilities.

3.0.3 The site shall have suitable geological conditions and shall avoid unfavourable geological ground such as serious landslides, debris flows and areas of subsidence. The selection of the site should avoid zones where karst is strongly developed; where this cannot be avoided, a special geological investigation shall be carried out and technical measures shall be taken in accordance with the provisions of the current national standard GB/T 51238 Technical standard for building foundations in karst regions.

3.0.4 Where a seismogenic fault is present at the site, the engineering effect of the fault shall be evaluated in accordance with the provisions of the current national standard GB 50011 Code for seismic design of buildings; the distance by which the site avoids a Holocene active fault shall also comply with the provisions of the current national standards GB 50011 and DL/T 5170 Technical code for geotechnical investigation of substations.

3.0.5 The site should avoid zones threatened by flood and by waterlogging; where the site is located in such a zone, flood control and drainage measures shall be taken. The flood control standard of the site shall comply with the provisions of the current national standard GB 50201 Standard for flood control.

3.0.6 Where the site is located on a hillside or at the foot of a hill, measures shall be taken to prevent mountain torrents and debris flows.

4 Electrical part

4.1 General requirements

4.1.1 The design principles of the main electrical connection of a high altitude substation are the same as those of a substation at conventional altitude. Since high altitude areas may suffer from a weak system network and severe climatic conditions, a connection arrangement of higher reliability may be selected for the substation after full technical justification.

4.1.2 In selecting the type of electrical equipment for a high altitude substation, account shall be taken not only of the effects of the reduced air pressure on external insulation and on heat dissipation, but also of the combined effect of environmental conditions such as high seismic intensity, extreme low temperature, strong ultraviolet radiation and strong wind and sand.

4.1.3 The design of a high altitude substation shall take account of the high number of thunderstorm days that accompanies the terrain and the altitude, and the arrangement of the surge arresters shall be determined by calculation of the incoming lightning surge.

4.1.4 The design of the substation should reduce the amount of construction work carried out on site.

4.2 Selection of electrical equipment

4.2.1 The selection of the type of the main transformer, the shunt reactor and similar equipment of a high altitude substation shall be determined by a comprehensive comparison of the cost of the equipment and the cost of transporting large components.

4.2.2 A 110 kV to 330 kV main transformer should be a three-phase transformer; a 500 kV main transformer should be a single-phase transformer, though a three-phase transformer may also be used depending on the transport conditions; a 750 kV main transformer should be a single-phase transformer.

4.2.3 The cooling method of a transformer in a high altitude area shall be selected reasonably according to the effect of the actual project environment on heat dissipation.

4.2.4 The temperature rise limits of oil-filled equipment such as transformers and reactors shall be corrected for altitude in accordance with the requirements of the current national standard GB 1094.2 Power transformers - Part 2: Temperature rise for liquid-immersed transformers.

4.2.5 In areas where the minimum annual temperature is minus 25 degrees Celsius or below, oil-filled equipment such as transformers, reactors and instrument transformers shall use insulating oil of low pour point.

4.2.6 Where the extreme minimum ambient temperature of the substation is below the liquefaction temperature of SF6 gas, outdoor switchgear shall use heating measures or gas mixture switchgear.

4.2.7 The seals of the outdoor electrical equipment of a high altitude substation shall use materials with strong resistance to ageing.

4.2.8 In areas of strong wind and sand, the seals of outdoor electrical equipment shall have corresponding wind and sand protection measures.

4.2.9 The capacity of each battery bank of the DC power system in a high altitude substation shall be corrected according to the derating requirements provided by the manufacturer.

4.2.10 The capacity of the uninterruptible power supply in a high altitude substation shall be corrected according to the derating requirements provided by the manufacturer, or in accordance with the provisions of the current industry standard DL/T 5491 Code for design of AC uninterruptible power supply systems for electric power engineering.

4.2.11 Where a diesel generator is used as the station service power source of a high altitude substation, the output of the diesel generating set shall be corrected for altitude in accordance with the requirements of the current national standard GB/T 6072.1 Reciprocating internal combustion engines - Performance - Part 1: Declarations of power, fuel and lubricating oil consumptions, and test methods - Additional requirements for engines for general use.

4.3 Selection of conductors and hardware

4.3.1 The long-term permissible current carrying capacity of the conductors of a substation below 4 000 m altitude shall be corrected in accordance with Table 5.1.5 of the current industry standard DL/T 5222 Code for design of conductor and electrical equipment selection; above 4 000 m it shall be determined by test.

4.3.2 The selection of the conductors in a high altitude substation shall take account of the effect of altitude on the corona inception voltage. The cross-section and the bundle configuration of the conductors shall satisfy the requirements on corona, radio interference and audible noise. The critical corona voltage of conductors at 110 kV and above shall be greater than the maximum operating voltage at the point where the conductor is installed. The maximum working electric field strength at the conductor surface should not be greater than 85 percent of its surface corona inception field strength.

4.3.3 Hardware in high altitude areas shall be designed for field grading and corona prevention, and shall be verified by electrical test.

4.3.4 The maximum working field strength at the surface of the hardware should not be greater than 85 percent of its surface corona inception field strength.

Remaining clauses in the full document

  • 5 Civil part
  • 6 Environment protection, soil and water conservation
  • 7 Labour safety and occupational health

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 75 pages — is available in the English PDF.

Similar standards

GB 50011|GB 50201|GB 1094.2|DL/T 5222|DL/T 5491|GB/T 6072.1

How to Buy NB/T 11513-2024

  1. 1Add to cart. Click the "Buy NB/T 11513-2024" button on this page. You can add more standards before checkout.
  2. 2Checkout. Enter your email and billing details. Payment is processed securely by Stripe (cards, Apple Pay, Google Pay supported).
  3. 3Instant delivery (0–9 sec). Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
  4. 4Invoice included. A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
75 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

NB/T 11513-2024

$935.00

$795.00for partners