GB/T 14536.15-2022Automatic electrical controls—Part 15: Particular requirements for humidity sensing control (English PDF)
电自动控制器 第15部分:湿度敏感控制器的特殊要求
Also coversGBT14536.15-2022
This is a limited preview
Buy now to download the full PDF
Need quotation for your management?
Get a formal quotation for GB/T 14536.15-2022 in 30 minutes.
Issued by
State Administration for Market Regulation; Standardization Administration of China
Level / Type
National · Recommended
Issue date
December 30, 2022
Implementation date
July 1, 2023
Scope
GB/T 14536.15-2022 is the English-translated version of 电自动控制器 第15部分:湿度敏感控制器的特殊要求.
GB 14536.1 of the chapter is applicable except as follows.
Found what you need?
Document preview — GB/T 14536.15-2022
National Standard of the People's Republic of China
- ICS
- 97.120
- Classification
- K32
Issued by: State Administration for Market Regulation; Standardization Administration of China
Contents
- 1 Scope and normative references1
- 2 Definitions1
- 3 General requirements1
- 4 General notes1
- Rating 15
- 6 Category1
- 7 Profile2
- 8 Protection against electric shock2
- 9 ground protection measures2
- 10 Terminals and terminations2
- 11 structural requirements2
- 12 moisture and dust2
- 13 Electric strength and insulation resistance2
- 14 Fever2
- 15 Manufacturing deviation and drift2
Foreword
All technical content in this section is mandatory.
GB 14536 "Household and similar electrical automatic controller" is divided into two parts.
--- Part 1.General requirements;
--- Part 2.Particular requirements.
Special requirements and consists of the following components.
--- GB 14536.3 - Particular requirements for thermal motor protectors (IEC 60730-2-2, IDT);
--- Particular requirements GB 14536.4 tubular fluorescent lamp ballasts for thermal protectors (IEC 60730-2-3, IDT);
--- GB 14536.5 sealed and semi-hermetic motor - compressor motor thermal protection Particular requirements (IEC 60730-2-4,
IDT);
--- Particular requirements GB 14536.6 automatic electrical burner control systems (IEC 60730-2-5, IDT);
--- GB 14536.7 pressure sensitive electrical controls - Particular requirements (idt IEC 60730-2-6);
--- GB 14536.8 Particular requirements for timers and time switches (idt IEC 60730-2-7);
--- GB 14536.9 Particular requirements for electrically operated water valves (including mechanical requirements) (IEC 60730-2-8, IDT);
--- GB 14536.10 - Particular requirements for temperature sensing controls (IEC 60730-2-9, IDT);
--- GB 14536.11 Particular requirements for motor starting relays (IEC 60730-2-10, IDT) used;
--- GB 14536.12 Particular requirements for energy regulators (idt IEC 60730-2-11);
--- GB 14536.13 Particular requirements for electrically operated door locks (IEC 60730-2-12, IDT);
--- GB 14536.15 Particular requirements for humidity sensing controls (IEC 60730-2-13, IDT);
--- GB 14536.16 Particular requirements for electric actuators (idt IEC 60730-2-14);
--- GB 14536.17 special requirements of the float or electrode-sensitive automatic electrical water level sensing controller used in the boiler appliance
(IEC 60730-2-15, IDT);
--- GB 14536.18 - Particular requirements for household and similar use of the float type level controllers (IEC 60730-2-16, IDT);
--- GB 14536.19 Particular requirements for electrically operated gas valves, including mechanical requirements (IEC 60730-2-17, IDT);
--- GB 14536.20 Particular requirements for water and air flow sensing controls, including mechanical requirements (IEC 60730-2-18, IDT);
--- GB 14536.21 Particular requirements for electrically operated oil valves, including mechanical requirements (IEC 60730-2-19, IDT);
This section identical with IEC 60730-2-13.2006 "special for household and similar use automatic controller to humidity sensing controls
begging".
Part of this structure with IEC 60730-2-13.2006 same. In this section, there is a corresponding national standards, national standards incorporated by reference
Quasi; no national standards, IEC standards are incorporated by reference outlined.
For ease of use, this section made the following editorial changes.
a) instead of as a decimal by decimal comma ",". ",";
b) increase the national standard foreword;
c) with the "GB 14536.1" instead of "Part 1."
This part of GB 14536.1-2008 "Household and similar electrical controls - Part 1.General requirements" in conjunction.
This Part replaces GB 14536.15-1999 "Household and similar electrical controls - Particular requirements for humidity sensing controls."
Compared with GB 14536.15-1999 part of the main changes are as follows.
a) Chapter 7 in Table 7.2 has some changes;
GB 14536.15-2008/IEC 60730-2-13.2006
b) Chapter 15 Manufacturing deviation and drift representation has increased;
c) the name of several sections according to changes GB 14536.1 made the appropriate changes;
d) Appendix H (requires electronic control) made major changes.
Appendix H and Appendix AA This section is normative appendix.
This part is proposed by the China Electrical Equipment Industrial Association.
This part of the National Standardization Technical Committee household automatic control (SAC/TC212) centralized.
This section is drafted. Guangzhou CVC Testing Institute, Guangzhou Electric Apparatus Research Institute, Zhejiang Yan Thermostat Co., Ltd. Ningbo
Economic and Technological Development Zone Haixin Electric Technology Co., Ltd., Guangdong Kelon Air Conditioner Co., Ltd.
1 Scope and normative references
GB 14536.1 of the chapter is applicable except as follows.
1.1 Replacement.
This section applies to the use of these or equipment for use in household and similar electrical devices automatic humidity sensing controls,
It includes a controller for heating, air conditioning and similar applications. These devices can use electricity, gas, oil, solid fuel, solar energy, etc., or it
Their energy mix.
1.1.1 The following note instead of the second paragraph after the Note.
Note. in this section, "device" contains the word "appliance" and "control."
1.1.2 Replacement.
This section applies capable of reacting or humidity control Automatic electrical controls for mechanical or electronic operation.
1.1.3 Not applicable.
2 Definitions
GB 14536.1 of the chapter is applicable except as follows.
2.2 is defined by use classification controller
2.2.19 Addition.
Note. Normally, humidity sensing controls are operating controller.
increase.
2.2.101
Used to the humidity is maintained at a certain value or more, the following electric automatic controller or two specific values.
2.2.102
Used to control independently mounted or mounted living space humidity humidity sensing controls.
3 General requirements
This is applicable in GB 14536.1.
General Description 4 Test
This is applicable in GB 14536.1.
5 RATINGS
This is applicable in GB 14536.1.
Category 6
GB 14536.1 of the chapter is applicable except as follows.
6.3.9 Addition.
GB 14536.15-2008/IEC 60730-2-13.2006
6.3.9.101 --- humidity sensing controls.
6.3.9.102 --- Room humidistat.
7 Information
This is applicable in GB 14536.1.
8 Protection against electric shock
This is applicable in GB 14536.1.
9 ground protection measures
This is applicable in GB 14536.1.
10 Terminals and terminations
This is applicable in GB 14536.1.
11 structural requirements
GB 14536.1 of the chapter is applicable except as follows.
11.4.3 Addition.
NOTE. In Canada and the United States, may not be connected to the capacitor contact between the controller type 2 actions.
12 moisture and dust
This is applicable in GB 14536.1.
13 Electric strength and insulation resistance
GB 14536.1 of the chapter is applicable except as follows.
Table 13.2
Add the following note in e) is.
Note. For humidity sensing controls, the sample may need to provide specially calibrated for this test.
Fever 14
This is applicable in GB 14536.1.
15 Manufacturing deviation and drift
GB 14536.1 of the chapter is applicable except as follows.
15.1 Review.
Note 15.1 does not apply.
15.4 Addition.
Alternatively, you can use the operating value plus the tolerance value method declaration to represent the manufacturing tolerances declared and drift.
15.5.3 Addition.
15.5.3.101 expectations for self-regulation by the user controls, unless the manufacturer otherwise stated, to be set by the regulator adjustable wet
The maximum value of the range.
Operation 15.5.3.102 controller should not exceed 0.05A current sensing a sensing element to complete.
Circuit may be any convenient voltage, as long as it is possible to reliably exhibit the monitored operating condition.
GB 14536.15-2008/IEC 60730-2-13.2006
15.5.4 Not applicable.
16 Environmental Stress
This is applicable in GB 14536.1.
17 Durability
GB 14536.1 of the chapter is applicable except as follows.
17.1.3 Test procedures and conditions
increase.
17.1.3.101 moisture sensitive controller, you should start with the amount of manufacturers and testing agencies agreed to test Chapter 17.
17.8 automatic acceleration operation test
increase.
17.8.4.101 unless the manufacturer declares a higher number of cycles, automatic actions independently mounted controller and line controller with dynamic and artificial
As the number of cycles shall comply with Annex AA AA. Provisions 1.
Note. Canada and the United States applies the number of cycles, see Appendix AA, AA. Rule 2.
Test 17.16 special purpose controller
increase.
17.16.101 humidity sensing controls
--- 17.1 to 17.5 applies;
--- 17.6 applies to classified 1.Or M-2.M-type action, "X" value agreed by the manufacturer and testing body;
--- 17.7 applies;
--- 17.8 applies;
--- 17.9 applies; except.
--- 17.9.3.1 do not apply;
--- 17.10 ~ 17.14 apply.
17.16.102
NOTE. In the United States, if a controller has two or more electrical ratings (for example. inductive and resistive, or different current values at different voltages),
The controller according to a statement of not less than 25% of the number of times the durability of the number of times each test rating (if the number of durability equal to or declaration
To 30000 cycles), but the total period either on the sample than the number of times the durability of its declaration. However, at least one sample test
The total number of cycles equal to the number of times the durability of its declaration.
18 Mechanical strength
This is applicable in GB 14536.1.
19 Threaded parts and connections
This is applicable in GB 14536.1.
20 creepage distances, clearances and distances through solid insulation through
This is applicable in GB 14536.1.
21 heat, fire and tracking resistance
This is applicable in GB 14536.1.
GB 14536.15-2008/IEC 60730-2-13.2006
22 corrosion resistance
This is applicable in GB 14536.1.
23 Electromagnetic compatibility (EMC) emission requirements ---
This is applicable in GB 14536.1.
24 components
This is applicable in GB 14536.1.
25 normal operation
This is applicable in GB 14536.1.
26 Electromagnetic compatibility (EMC) requirements --- immunity
This is applicable in GB 14536.1.See Appendix H.
27 non-normal operation
This is applicable in GB 14536.1.See Appendix H.
28 Guidelines for the use of electronic disconnection
This is applicable in GB 14536.1.
GB 14536.15-2008/IEC 60730-2-13.2006
Fig GB 14536.1 FIG apply.
GB 14536.15-2008/IEC 60730-2-13.2006
appendix
GB 14536.1 Appendix, is applicable except as follows.
Appendix H
(Normative)
Requirements for electronic controllers
GB 14536.1 of the appendix, is applicable except as follows.
H. 6.18 by Software Category
H. 6.18.1 --- A class software
increase.
Note. In general, the use of software for humidity sensing controls are classified as Class A software.
H. 7 Information
Make the following changes to Table 7.2.
Information chapter, strip method
58a
increase.
Table H. 26.2.101 footnote a)
Increased requirements.
Type 2 humidity-sensitive controller output after operation
Conditions 101)
H. 26.2.103
H. 26.2.104
H. 26.2.105
101), for example, conductive or non-conductive, as applicable.
H. 11 structural requirements
H. 11.12 use the software controller
H. 11.12.8 replaced by the following sections explain.
NOTE. Table H. 7.2 The provisions of paragraph 71 values given by the applicable appliance standard.
H. 11.12.8.1 At the end of this clause to add the following explanation.
NOTE. Table H. 7.2 Section 72 applies a predetermined value by the appliance standard given.
H. 23 Electromagnetic compatibility (EMC) requirements --- immunity
H. 23.1.2 Radio frequency emissions
increase.
Integral electric load and humidity sensing controls are not subjected to this entry tests, because the results of these tests will be charged because the controller appliance
Affected, and also affected the measurement of radiation measuring device. If the manufacturer's request, the controller can also be stated in the conditions
carry out testing.
H. 26 Electromagnetic compatibility (EMC) requirements --- immunity
H. 26.2 Addition.
GB 14536.15-2008/IEC 60730-2-13.2006
After each test, shall be in accordance with Table H. One or more indicators 26.2.101 listed. 1)
1) In the original IEC as "table H.26.101", after the determination of a clerical error, the words "table H.26.2.101".
increase.
H. 26.2.101 If applicable, the controller should remain in its current state, and according to the party statement within Chapter 15 of the verification limits
Style action.
H. 26.2.102 controller shall meet the conditions shown in Table 7.2 in paragraph 101 of the statement, and should be followed as H. 26.2.101 in the normal
action.
H. 26.2.103 If you meet the controller Table 7.2 Item 101 declared conditions, should not be automatic or manual reset. Lost during normal operation
Waveform is a sine wave or meet Table 7.2 Section 53 of the declaration.
H. 26.2.104 controller remains in state Table 7.2 Item 101 declared. Non-self-resetting controller should only manually
Reset. When making operation to evacuate humidity conditions, the controller should be in accordance with H. The 26.2.101 action, or remain in H. 26.2.103 The
State declaration.
H. 26.2.105 controller may return to the initial state, and then press H. The 26.2.101 normal operation.
NOTE. If the controller in Table 7.2 under Item 101 state declaration, the controller can be reset, but when the humidity conditions so that action still exists, should again
Back to the declaration of the state.
H. 26.2.106 while the output of the controller and run the item 58a or item 58b declared in Table 7.2, the controller should meet
17.5 request.
Table H. According to the standard 26.2.101
Terms H26 test applies permissible according to the standard
Type 2 humidity sensing controls H. 26.2.101 H. 26.2.102 H. 26.2.103 H. 26.2.104 H. 26.2.105H. 26.2.106a)
H. 26.4 ~ H. 26.14 b b b a a x
Other humidity sensing controls H. 26.2.101 H. 26.2.102 H. 26.2.103 H. 26.2.104 H. 26.2.105H. 26.2.106a)
H. 26.8, H. 26.9 x x x
x = Allow; causing interference after a = action allows; the interfering action before allowing b =
a) because the output needs to determine the acceptability of the appliance, the guidelines apply only to integral or load controller.
H. 26.5 voltage sag and interruption of power supply network
H. 26.5.4 voltage fluctuation test
instead.
H. 26.5.4.3 humidity sensing controls shall be subjected to a given voltage of each test cycle three times, each test cycle interval 10s. For table
7.2 Item 101 requires the declaration of the humidity sensing controls, under the condition statement is subjected to three times per cycle, each subjected to the conditions in the non-declaration
Cycle 3 times.
H. 26.8 Surge immunity test
H. 26.8.3 Test Procedure
increase.
H. 26.8.3.101 for Table 7.2 requires the declaration of the controller Item 101, subjected to the test conditions in a statement three times in the non-declaration Article
Member under withstand twice.
GB 14536.15-2008/IEC 60730-2-13.2006
H. 26.9 Electrical fast transient/burst test
H. 26.9.3 Test Procedure
increase.
H. 26.9.3.101 controller 5 is subjected to tests. For the requirements stated in Table 7.2 Controller item 101, is applied at a position statement
3, the position of the non-declaration is applied twice.
H. 26.10 ring wave test
H. 26.10.5 Test Procedure
increase.
H. 26.10.5.101 Table 7.2 for required items declared in the controller 101, subjected to the test conditions in a statement three times in the non-declaration Article
Member under withstand twice.
H. 26.12 Radio electromagnetic field immunity
H. 26.12.2 conducted disturbances immunity
H. 26.12.2.2 Test Procedure
increase.
For the requirements stated in Table 7.2 controller Item 101, in the statement and the statement of the position of non-interference is applied respectively.
H. 26.12.3 radiated electromagnetic radiation field immunity Assessment
increase.
H. 26.12.3.101 Table 7.2 for required items declared in the controller 101, under the condition statement and statement of non-interference is applied respectively.
H. 26.13 Variation of power frequency impact test
H. 26.13.3 Test Procedure
increase.
For the requirements stated in Table 7.2 Controller item 101, under the conditions of declaration and non-declaration be tested separately.
H. 26.14 Power frequency magnetic field immunity test
H. 26.14.3 Test Procedure
increase.
For the requirements stated in Table 7.2 Controller item 101, under the conditions of declaration and non-declaration be tested separately.
H. 26.15 Conformity Assessment
H. 26.15.2 Addition.
Based on criteria in Table H. 26.2.101.
H. 26.15.4 Addition.
Based on criteria in Table H. 26.2.101.
H. 27 non-normal operation
H. 27.1.2 replace line 1 with the following.
The controller shall operate the following conditions. Also, the controller for Table 7.2 Item 101 requirements set out in the declaration and non-declaration conditions
They were tested under the conditions.
Increase in Appendix.
GB 14536.15-2008/IEC 60730-2-13.2006
Appendix AA
(Normative)
The number of cycles
AA. The number of cycles is independently mounted and with a line controller
Controller type automatic operation manual operation
Temperature sensing controls 6,000,600
Room humidistat 60,000,600
AA. The minimum number of cycles are independently mounted and with a line controller (Canada and the United States applicable)
Humidity sensing controls
A dehumidifying a humidifying
Type 1 Type 2 Type 2 Type 1
Automatic action
initial
The maximum number of cycles/min
At last
The maximum number of cycles/min
1b
75,000
25,000
1b
30,000
1b
75,000
25,000
1b
Manual operation
initial
The maximum number of cycles/min
At last
The maximum number of cycles/min
1b
1b
1b
1b
Manual work
The maximum number of cycles/min
a magnetic, manual and motor actuator switch or similar switch, and quickly closed when idle instead of gradually closed switch, on a per-minute
Clock rate of six cycles of test.
b all controllers, are (50 ± 20)% of on-time test, humidity sensing controls to a low rate of change to this test.
c does not involve the current test can be used in any convenient rate.
GB 14536.15-2008/IEC 60730-2-13.2006
......
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — all pages — is available in the English PDF.
Referenced standards
Normative references
GB 14536.1
How to Download GB/T 14536.15-2022
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB/T 14536.1-2022 — Automatic electrical controls—Part 1: General requirements
GB/T 14536.10-2022 — Automatic electrical controls—Part 10: Particular requirements for temperature sensing control
GB/T 14536.13-2022 — Automatic electrical controls - Part 13: Particular requirements for electrically operated door locks
Secure payment via Stripe
Payments accepted
GB/T 14536.15-2022
$295.00