GB 19215.3-2012Cable trunking and ducting systems for electrical installations -- Part 2: Particular requirements -- Section 2: Cable trunking systems and cable ducting systems intended for underfloor and flush floor installations (English PDF)
电气安装用电缆槽管系统 第2部分:特殊要求 第2节:安装在地板下和与地板齐平的电缆槽管系统
This is a limited preview
Buy now to download the full PDF (16 pages)
Need quotation for your management?
Get a formal quotation for GB 19215.3-2012 in 30 minutes.
Issued by
Standardization Administration of China
Level / Type
National · Mandatory
Issue date
November 5, 2012
Implementation date
May 1, 2013
Scope
GB 19215.3-2012 is the English-translated version of 电气安装用电缆槽管系统 第2部分:特殊要求 第2节:安装在地板下和与地板齐平的电缆槽管系统.
GB 19215.3-2012 — Alternative. This section provides installed in the floor and the floor is flush with the classification of cable trunking and ducting systems, and structural requirements, anti-flame spread, mechanical properties, External influences technical requirements.
This section applies to the installation under the floor and flush with the floor cable trunking and ducting systems. The fluted tube system is used and, if necessary, to accommodate for Separated conductors, cables or cords and/or other electrical equipment.
This section applies to the installation have been completed or under the floor and the floor has been completed, flush-mounted cable trunking and ducting systems and system components.
This section does not apply to conduit, cable tray or ladder (cable trays), as well as in the present system of current-carrying parts. Note 1. Models and Usage Figure 101 and 102.
Note 2. Figure 101 shows the type and design of many systems, sub-standard being considered. Note 3. Some or all of the system on the ground are not included in this part of the standard, but it may be included in the amended standard part or other part 2 standards.
Found what you need?
Document preview — GB 19215.3-2012
National Standard of the People's Republic of China
- ICS
- 29.120.10
- Classification
- K 65
Issued by: Standardization Administration of China
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 4 2 General requirements
- 5 Test 2 General requirements
- 6 Category
- 7 Mark
- 8 Size
- 9 Structure
- 10 Mechanical properties
- 11 Anti-flame spread
- 12 Electrical properties
- 13 8 external influences
- Appendix A (informative)
- Annex AA (informative)
Foreword
Chapter 9 of this section, Chapter 10, Chapter 11, Chapter 12, Chapter 13 is mandatory, the rest are recommended.
GB 19215 "Electrical Installation Cable trunking and ducting systems" is divided into two parts.
--- Part 1. General requirements
--- Part 2. Particular requirements Cable trunking and ducting systems for mounting on a wall or ceiling. --- Section 1
--- Section 2. installed in the floor and flush with the floor cable trunking and ducting systems
--- The first three files for future .( blank)
--- Section 4. household electrical column this section is GB 19215 Part 2, Section 2.
This section drafted in accordance with GB/T 1.1-2009 given rules.
This section uses the translation method identical with IEC 61084-2-2:2003 (first edition) Part 2-2 "Electrical installation Cable trunking and ducting systems Score. Particular requirements installed under the floor and flush with the floor cable trunking and ducting systems. " Consistency correspondence between this part of international documents and normative references of the following documents.
--- GB/T 19215.1 electrical installations cable trunking and ducting systems - Part 1. General requirements (GB/T 19215.1-2003, IEC 61084-1:1991 A1.1993, MOD) this part of IEC 61084-2-2:2003 made the following editorial changes.
--- According to GB/T 1.1 relevant provisions in Chapter 1, "scope" in the first line of supplements "This section provides installed in the floor and the ground Classification board flush cable trunking and ducting systems, and structural requirements, anti-flame spread, technical requirements for mechanical properties, external influences. "
--- According to GB/T 1.1 relevant provisions in Chapter 2, "Normative references" supplemented with IEC 61084-1 name.
--- Increase the national standard foreword;
--- "This standard" be replaced by "of this section." this part is proposed by the China Electrical Equipment Industrial Association.
This part of the National Electric annex Standardization Technical Committee (SAC/TC67) centralized.
This section drafted by. China Electric Apparatus Research Institute Co., Ltd., Hangzhou Hongyan Electric Co., Ltd., Foshan Gaoming Gu plastic limited the company, Liansu Technology Industrial Co. Ltd., the Bulls Group Co., Ltd. Zhejiang Yuehua Telecommunication Co., TCL- Legrand International Electrotechnical (Huizhou) Co., Ltd., Zhejiang Hengtai Electrical Co., Ltd.
1 Scope
Alternative.
This section provides installed in the floor and the floor is flush with the classification of cable trunking and ducting systems, and structural requirements, anti-flame spread, mechanical properties, External influences technical requirements.
This section applies to the installation under the floor and flush with the floor cable trunking and ducting systems. The fluted tube system is used and, if necessary, to accommodate for Separated conductors, cables or cords and/or other electrical equipment.
This section applies to the installation have been completed or under the floor and the floor has been completed, flush-mounted cable trunking and ducting systems and system components.
This section does not apply to conduit, cable tray or ladder (cable trays), as well as in the present system of current-carrying parts.
Note 1. Models and Usage Figure 101 and 102.
Note 2. Figure 101 shows the type and design of many systems, sub-standard being considered.
Note 3. Some or all of the system on the ground are not included in this part of the standard, but it may be included in the amended standard part or other part 2 standards.
2 Normative references
The following documents for the application of this document is essential. For dated references, only the dated version suitable for use herein Member. For undated references, the latest edition (including any amendments) applies to this document.
IEC 61084-1 for electrical installations cable trunking and ducting systems - Part 1. General requirements (Cabletrunkingandducting systemsforelectricalinstalations-Part 1. Generalrequirements) of this chapter apply to the following modifications.
increase.
GB/T 2423.51-2000 Environmental testing for electric and electronic products Part 2. Test methods - Test Ke. Flowing mixed gas corrosion Erosion Testing (idtIEC 60068-2-60.1995)
3 Terms and Definitions
IEC 61084-1 of this chapter apply to the following modifications.
Increase definition.
3.101
Cable trunking and ducting systems underfloorcabletrunkingsystemorcableductingsystem underfloor A method of installing a cable channel pipe system under the floor, in addition to its floor mount other components have been completed by an upper ground plate Protected material is subjected to external mechanical loads, flooring materials in normal use can reduce the load of the load (see Fig. 103) under the conditions of use of the groove pipe.
3.102
Floor flush cable trunking and ducting systems flushfloorcabletrunkingsystemorcableductingsystem Cable trunking and ducting system for flush-mounted and floor, which in addition to the floor mounting member other than through all elements except the upper part it has already been completed to protect flooring and subjected to an external mechanical load and flush-mounted in the inner surface of the floor has been completed. Unprotected surface is considered Bear truck load surface (see Fig. 104).
3.103
Completed floor finishedfloor it may be made of concrete, wood or similar material to withstand the load floor, and covered with carpet, tile, paint, parquet or similar supporting floor covering. Floor coverings may be fixed by a cement or asphalt on a composite floor.
3.104
Flush with the floor system components flushfloorsystemcomponent all except one kind through the upper part than has already been completed and to protect flooring from external mechanical loads on the system in normal use System components, and its nominal flush-mounted in the inner surface of the floor has been completed. No protection is considered to bear the load surface load surface.
3.105
Floor mount (when idle) floorserviceunit (whennotinuse) no cables and/or wires to the floor mount appliances on.
3.106
Floor mount (when used) floorserviceunit (wheninuse) There are cables and/or wires to the floor mount appliances on.
3.107
Cable anchorage Especially for reducing distortion conductor terminals or head end or prevent a device separate from the cable housing.
3.108
Floor dry process dry-treatmentoffloor not only a small amount of liquid to clean the liquid and/or process or care floors. Cleaners needed to be able to achieve such a quality.
It does not form puddles and wet floor covering.
Note. The dry process Example. sweep with a broom or a blanket for cleaning, vacuuming, brushing, cleaning powder dry, dry cleaners treatment, carpet cleaning agent and cleaning Waste disposal (solid material containing chemical cleaning agents, such as wet sawdust and wet laundry, etc.).
3.109
Floor wet process wet-treatmentoffloor Use liquid detergent to clean and/or processes of care floors. A period of time after such treatment inevitably forming puddles or it will wet floor covering.
NOTE. Wet Processing example. water, artificial or machine scrub.
4 General requirements
IEC 61084-1 of this chapter apply to the following modifications.
Increase in the third paragraph.
Constituting the system components necessary equipment should comply with the latest standards.
5 General requirements, tests
IEC 61084-1 of this chapter apply to the following modifications.
5.1 Alternative second paragraph as follows.
For the test, and system components comprising an insulating synthetic material, samples should be at a temperature of 60 °C ± 2 °C in a row after holding 240h operating.
Category 6
IEC 61084-1 of this chapter apply to the following modifications.
Addition of provisions.
Classification by floor approach 6.101 6.101.1 floor dry treatment of cable trunking and ducting systems.
When idle 6.101.2 floor mount, floor wet treatment of cable trunking and ducting systems.
When 6.101.3 floor mount use, floor wet treatment of cable trunking and ducting systems.
Protection features by 6.102 floor mount when used against impact classification 6.102.1 floor mount a protective cable trunking and ducting systems.
6.102.2 floor mount unprotected cable trunking and ducting systems.
7 Logo
IEC 61084-1 of this chapter apply to the following modifications.
7.1 Replace the first paragraph as follows.
Each cable tray/cable pipe and tank/pipe fittings shall be marked with the manufacturer or responsible vendor's name or trademark and product identification.
Addition of provisions.
7.101 manufacturers should provide all the necessary information about how to properly assemble and safely used in their profile. Information should this includes.
--- Various constituent elements of the system;
--- System components and assembly functions;
Available cross section --- pipe or tank section;
NOTE. Some of the accessories will be reduced to the internal space of cable placement.
--- Accessory to install and use on any limitations on available space;
--- Chapter 6, according to the classification system;
--- Reach the guidance announcement properties.
7.102 comply 6.101.1 classification system element floor dry treatment is flush with the floor should be clearly marked, indicating that they do not fit Mounted on the floor in a wet process. These marks after the end of the electrical installation should still clearly visible. Available as a graphic symbol or Shaped pattern as a logo.
7.103 floor mount should be clearly marked warning to avoid use of inappropriate plug, it may damage the equipment plug, cord or outlet.
This warning can be represented by a graphic symbol or pictogram.
7.104 Compliance is checked by observing the requirements of 7.1 and 7.101 ~ 7.103.
Size 8
IEC 61084-1 This clause does not apply.
9 Structure
IEC 61084-1 of this chapter apply to the following modifications.
9.4.1 In the second paragraph in the "installed" alternative "normal use." 9.6.2 in the first paragraph in the "40 °C" replaced by "60 °C".
Addition of provisions.
9.101 installed under the floor and flush with the floor cable channel cable channel cable systems and pipe systems covered in the normal course by Often by external mechanical load, avoid moving and accidental opening.
Compliance is checked by observation and tests to check the provisions of 10.5.
9.102 comply 6.102.1 types of flooring installation and electrical parts should be protected against direct outlet collision impact during use. This warranty Protection should be effective and will not cause damage to the electrical sockets and cables.
Compliance is checked by the test specified in 10.3 to check.
9.103 should be able to safely install the following.
--- The floor flush cable trunking and ducting systems installed in the floor;
--- The floor mounting member installed on the system and/or floor;
--- The electrical connections to the floor mount.
Compliance is checked by experiment and 10.5.103 10.5.102 provisions to check.
9.104 The manufacturer shall provide an effective way to cover exposed during installation of underfloor cable trunking and ducting systems to prevent damage.
Compliance is checked by the test specified in 10.5.101 checked.
9.105 under the floor and flush with the floor of the cable channel pipe systems for wire and cable through the opening opened should be protected effectively against Only damage. When not in use, it should be completely closed by covering the surface around.
Note. Examples of a surface is covered around the floor frame mounting member.
Underfloor and floor flush cable channel pipe systems for wire and cable through the opening opened, if it is in one direction the size of not more than 20mm, then, during use should not be closed.
Compliance is checked by inspection and measurement checks.
Cable trunking and ducting systems mounted flush with the floor of 9.106, floor mounting parts and accessories shall comply with the provisions of 6.101 and classification 6.6.1,6.6.2 standard.
Compliance is checked by GB 4208 and 13.101 predetermined test to check.
9.107 pieces of equipment for installation of floor space should be at least degree of protection IP20.
Compliance is checked by tests to check the GB 4208 regulations.
9.108 pairs of those particular devices during normal use often move should take protective measures to ensure that its components will not make long-term the damaged with.
Compliance is checked by observation to check.
9.109 If the cable anchorage, shall apply in accordance with the manufacturer's instructions may be connected to various types of cable. 1)
1) where the original language. "Note. In the UK, the accessory cable anchorages comply with their own standards without the necessity to comply with the requirements of this provision of the proposed" Compliance is checked by observing and following test to check.
In line with a designed maximum outer diameter of the cable anchorage cables or wires fitted on the cable anchor. When the clamping screw is applied IEC 61084-1 Table 2 lists the value of two-thirds of the torque to tighten the screws.
To keep the sample 30min ~ 31min at 60 °C ± 2 °C temperature. Similarly the sample at this temperature, with 20 1 0N tension 60s ~ 65s to maintain the role of cable or wire.
In line with a cable or wire assembly cable anchorage minimum design diameter on the cable anchorage, the test is repeated once.
After each test, the cable or wire in the cable anchor should not move more than 3mm and the cable or wire insulation should not wear.
Under 9.110 during normal use is often embedded in mortar debris material flooring and floor flush cable trunking and ducting systems, should be given protection to prevent debris from entering the mortar material.
In normal use, leading to the installation in cable ducts and underfloor pipe system inside the opening flush with the floor, it should be set lower than the Completion of the highest edge of the floor, and in a direction should not be wider than 7mm.
Compliance is checked by inspection and measurement checks.
Note 1. The maximum cross-sectional width dimension of the opening in the mixing ratio of cement-based mortar as follows. 1 part cement, sand (particle size reaches 7mm) and two fitness Amount of water (water - cement ratio. 0.4L/kg ~ 0.5L/kg).
Note 2. The proportions of water and cement (L/kg) showed that the volume and quality of cement than water.
150L water/300kg cement = 0.5L/kg
Note 3. When the mortar is not used when the ratio according to Notes 1 and 2, the reference to the manufacturer's instructions to determine the width of the opening value.
10 Mechanical properties
IEC 61084-1 of this chapter apply to the following modifications.
10.1 Replacement.
Installed under the floor and flush with the floor cable trunking and ducting systems shall have adequate mechanical strength.
Compliance is checked by the test specified in 10.2 to 10.5 to check.
10.2 NA
10.3 Impact test
Alternative.
10.3.1 Storage and transportation impact test
10.3.1.1 The test is in three cable length 250mm ± vat segment cable or pipe 5mm carried on.
Before the test, the insulation system and composite material components should be long-term use in the temperature range Maximum temperature in continuous treatment specified in Table 1 240h ~ 250h.
10.3.1.2 The test apparatus shown in FIG. 2 is placed in a foamed EPR sponge pad, sponge pad thick when uncompressed 40mm ± 1mm, a density of 450kg/m3 ~ 550kg/m3.
The sample was frozen into the box, the inside temperature should be maintained during storage and transport the samples in Table 1 as specified in the appropriate temperature.
After 10.3.1.3 120min ~ 125min, each sample will turn inside out from the freezer and immediately placed in the test apparatus in positive in the normal position.
In the specimen from the freezer box out of the 10s, let the hammer fall on the weakest area of the sample up to the implementation of a shock. Hammer Weight 0.5kg ~ 0.505kg, drop height 100mm ± 1mm.
The test is not suitable for similar parts off hole, the diaphragm and the like.
10.3.1.4 After the test, the sample may not appear broken signs, nor now come under normal or corrected vision without magnification, of visible any security may be reduced cracks or similar damage.
Note. Any crack in the partition, as without compromising electrical safety or normal users, is negligible.
10.3.2 Installation and use of the impact test
10.3.2.1 Test in three length on 250mm ± 5mm groove section or pipe sections will be, if any, to provide system components.
Assembly and fixed predetermined sample according to the manufacturer's instructions in a thick 20mm ± 2mm on wood fiberboard.
Before the test, the insulation system components and composite components should be long-term use in specified in Table 1 at a temperature range of maximum continuous temperature Processing 240h ~ 250h.
10.3.2.2 Impact test device structure shown in Figure 105, which is mounted on a wall or solid enough to support the structural strength.
10.3.2.3 The sample was placed in a freezer box, keeping the temperature during the installation and use as specified in Table 1 in the corresponding temperature.
After 120min ~ 125min, each sample will turn inside out from the freezer and immediately placed in the test apparatus in normal Location in.
The specimen in the freezer from the inside out to 10s, and let the hammer fall on the surface of the sample as much as possible perpendicular to the direction of the sample the weakest area of the implementation of a shock.
The test is based on the impact test value table 101 required by regulation.
Table 101 impact value
6.2 Mechanical properties according to classification Energy value (approximately) Quality Hammer (Tolerance 10%) kg Drop height ± 1% mm Very small 0.5 0.5 100 Small 1.0 1.0 100 Medium 2.0 2.0 100 Great 6.0 2.0 300 Very large 20.0 6.7 300 the test is not suitable for off hole, the diaphragm and other parts of the ends of the thickness of 50mm or less similar.
10.3.2.4 After the test, the sample may not appear broken signs, nor now come under normal or corrected vision without magnification, of visible any security may be reduced cracks or damage. And the cover and accessories should not be rushed to the exit.
Note. Any crack in the partition, as without compromising electrical safety or normal users, is negligible.
10.4 Linear bending test
Not applicable
10.5 External load test
Alternative.
10.5.101 External mechanical load stress intensity
Installed in the floor and a floor flush cable trunking and ducting systems should have sufficient mechanical strength to withstand transport, storage, security Installation and normal use of external mechanical loads.
Compliance is checked by tests to check ~ 10.5.104 10.5.102 provisions.
A summary of the test are given in Annex AA.
10.5.102 under the floor and flush with the floor of the cable tray section and pipe external load test in the installation process Section and pipe cable tray under the floor according to the provisions of 10.5.102.1 test, flush with the floor of the cable tray section and pipe press Provisions 10.5.102.2 be tested.
Each test requires three samples. The length of the sample is 250mm ± 5mm.
Sample according to Table 1 at a temperature of permanent use of the classification process 120min ~ 125min after 10.5.102.1 and 10.5.102.2 specified test.
10.5.102.1 in the external load test cable tray section and the pipe section is installed under the floor, the sample is placed on a flat plate opposed on. A sample is placed in the middle edge length of 50mm ± 1mm and angular radius of about 1mm steel cube.
In the case of cable attached to the pipe under the floor has multiple intervals, the partition walls have a static effect, select the maximum interval of a central location.
The size of a vertical force of 750N ± 10N central role in the cube, 2min time duration (see Fig. 106).
10.5.102.2 flush with the floor of the cable tray segments and segment external load test, the sample is placed on a support pad feet, according to the manufacturer Manufacturer's instructions, from the same side of the supporting feet of L. Support feet and make the bottom of the sample from the flat plate is adjusted to 10mm ± 2mm. The size of a central vertical force of 750N ± 10N applied to the cube, lasted 2min ± 5s (see Figure 107).
10.5.102.3 and 10.5.102.2 10.5.102.1 after the test, the sample may not appear broken signs, nor come to normal now, as the any visible crack the case or to correct vision without additional amplification. After the external load is removed 1min permanent deformation shall not exceed 3mm.
10.5.103 under the floor and flush with the floor section and pipe cable tray truck load in continuous use in the test If the element is related to the system or pipe groove section, the specimen length shall be 250mm ± 5mm. Three samples in Table 1 should be in compliance Given the long-term use at the maximum temperature for processing 120min ~ 125min. Central surface of the sample is easily stampede, as defined in accordance with Table 102 the amount of force used to implement a test roller external load, time sequentially over 60s ± 1s, time to implement load in a direction perpendicular to the surface of 2min ± 5s. In samples with multiple intervals, the separating element has a static force of circumstances, to choose the largest central spaced locations. The test Mortem roller diameter of 50mm ± 0.5mm, length 20mm ± 1mm, angular radius of about 1mm (see Figure 108).
Note. The material provides support around the mortar and Static support can be simulated in the test by an appropriate method.
After the test, the sample may not appear broken signs, nor draw any crack now under normal or corrected vision without magnification, of visible Marks, appears partial transition type must not exceed 4mm. After the external load is removed 1min permanent deformation should not exceed 3mm.
Electrical Safety can not be compromised.
Table 102 external load test urging size
Classification force Size of the force (± 10N) Light 1500 Medium 2000 Heavy 2500 Heavy 3000 Fixed electrical installation test 10.5.104
10.5.104.1 Output socket
Follow the manufacturer's installation instructions to install the following three floor samples.
Electrical installation of a mounting device on a floor mount or related system components samples. When this system is a vat segment or element by pipe, then the electrical length than the length of the sample mounting device 100mm ± 5mm, and not less than 250mm.
Note. If desired, other system components may also be included to prevent electrical installation device activity.
If the results of the test depends on the temperature, then at 60 °C ± 2 °C temperature test.
1.5 times the maximum plug withdrawal force of the tension and pressure to electrical installation angle of the plane direction of 45 ° ~ 90 °, followed by acting on the electrical the most un...
......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 16 pages — is available in the English PDF.
Referenced standards
Normative references
IEC 61084
How to Download GB 19215.3-2012
- 1
Add to cart
Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.
- 2
Checkout
Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).
- 3
Instant delivery (0–9 sec)
Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.
- 4
Invoice included
A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.
Related Standards
GB 11118-2026 — Hydraulic fluids (L-HL, L-HM, L-HV, L-HS and L-HG type)
GB 11557-2026 — Provisions for protecting drivers from injury by the steering mechanism of motor vehicles
GB 12021.4-2026 — Maximum allowable values of the energy consumption, water consumption and grades for electric washing machines and washer-dryers
Secure payment via Stripe
Payments accepted
GB 19215.3-2012
$295.00