DL/T 911-2016Frequency response analysis on winding deformation of power transformers (English PDF)

电力变压器绕组变形的频率响应分析法

Preview PDF

This is a limited preview

Buy now to download the full PDF (11 pages)

Need quotation for your management?

Get a formal quotation for DL/T 911-2016 in 30 minutes.

Issued by

National Energy Administration

Level / Type

National · Recommended

Issue date

February 5, 2016

Implementation date

July 1, 2016

Scope

DL/T 911-2016 is the English-translated version of 电力变压器绕组变形的频率响应分析法.

DL/T 911-2016 is the Chinese standard "Frequency response analysis on winding deformation of power transformers". Its scope clause reads: This standard specifies the basic requirements for detecting transformer winding deformation by frequency response analysis.

This standard applies to power transformers with voltage levels of 66kV and above and other transformers for special purposes. Its clauses include terms and definitions; detection principle; requirements for detection instruments; detection method; analysis and judgment of winding deformation.

It was issued by the National Energy Administration on 2016-02-05 and took effect on 2016-07-01.

Found what you need?

Document preview — DL/T 911-2016

National Standard of the People's Republic of China

ICS
27.100
Classification
F 24

Issued by: National Energy Administration

Contents

  • Foreword...3
  • 1 Scope...5
  • 2 Normative references...5
  • 3 Terms and definitions...5
  • 4 Detection principle...6
  • 5 Requirements for detection instruments...8
  • 6 Detection method...9
  • 7 Analysis and judgment of winding deformation...11

1 Scope

This standard specifies the basic requirements for detecting transformer winding deformation by frequency response analysis.

This standard applies to power transformers with voltage levels of 66kV and above and other transformers for special purposes.

2 Normative references

The following documents are essential to the application of this document. For the dated documents, only the versions with the dates indicated are applicable to this document;

for the undated documents, only the latest version (including all the amendments) is applicable to this standard.

DL/T 1093 Guide for reactance method to detect and diagnose winding deformation of power transformer

3 Terms and definitions

The following terms and definitions apply to this document.

3.1

Winding deformation

Refers to the axial or radial dimensional changes of power transformer windings under the action of electric or mechanical forces, when they are subjected to short- circuit current shock or collision during transportation; it is usually manifested as local twisting, bulging or displacement of windings.

3.2

Bilateral network

Refers to a network with a pair of input ports and a pair of output ports. If the network is composed of linear resistors, inductors (including mutual inductance), capacitors, meanwhile it does not contain any independent power supply inside, it is called a passive linear bilateral network.

3.3

Transfer function

The ratio of the output to the input of a passive bilateral network, which is expressed in Laplace transform form. The distribution of the poles and zeros of the transfer function is closely related to the internal component parameters, connection method, port connection impedance of the bilateral network.

3.4

Frequency response

Refers to the relationship between the transfer function H(jomega) of the network and the angular frequency omega in the sinusoidal steady state. The relationship between the amplitude of H(jomega) and the frequency omega is usually called the amplitude-frequency response; the relationship between the phase of H(jomega) and the frequency omega is called the phase-frequency response.

4 Detection principle

Under the action of a high frequency voltage, each winding of the transformer can be regarded as a passive linear bilateral network, which is composed of distributed parameters such as linear resistance, inductance (mutual inductance), capacitance.

5 Requirements for detection instruments

5.1 Basic requirements for detection instruments

For the basic requirements of transformer winding deformation tester, please refer to

Appendix A.

5.2 Sweep frequency detection range

The sweep frequency detection range shall include the frequency band of 1kHz ~

1000kHz.

5.4 Sweep frequency accuracy

The frequency accuracy of the sine wave signal output by the signal source shall not exceed 0.01%.

5.5 Scanning frequency interval

The scanning frequency interval should be 1kHz.

5.6 Impedance matching method

The output impedance RS of the sine wave signal output source US of the detection instrument shall be 50ohm; the input impedance of the two signal detection terminals U1 and U2 shall not be lower than 1Mohm; a 50ohm matching resistor R shall be installed between the signal response terminal and the common terminal (see Figure 1).

5.7 Detection accuracy

The detection instrument shall have a dynamic detection range of -100dB ~ 20dB; the absolute error of detection within the range of -80dB ~ 20dB shall be less than 1dB.

5.10 Data query function

The search function can be used to query the historical data of the same model, the same manufacturer and the transformer.

6 Detection method

6.1 Detection condition requirements

6.1.1 Detection shall not be carried out in thunderstorms, rain, snow and other weather.

The detection shall strictly implement the requirements of the power safety work regulations; it shall strictly implement the organizational and technical measures to ensure safety. The test personnel shall be trained and have the ability to conduct on-site tests.

6.1.3 Before testing, all leads connected to the end of the transformer bushing shall be removed; the removed leads shall be as far away from the tested transformer bushing as possible.

6.2 Wiring requirements

6.2.1 All wiring shall be stable and reliable. Special wiring clamps shall be used to reduce contact resistance.

6.2.2 The same wiring method shall be used for the same transformer or the same model.

The test cable and ground lead on the excitation end and the response end can be led down along the porcelain sleeve of the bushing. The ground wire cannot be entangled and shall be electrically connected to the metal box of the transformer nearby, to maintain good high-frequency grounding performance.

6.3 Wiring method

6.3.1 According to the connection structure of the transformer winding, select the

excitation end (input end) and response end (measurement end) of the winding to be tested according to Figure 2; the ends of other windings are suspended.

7 Analysis and judgment of winding deformation

7.1 Analysis and judgment principle

The frequency response analysis method is used to judge the deformation of transformer windings. The frequency response data curves of three-phase windings of the same voltage level are mainly compared longitudinally, laterally, comprehensively; the changes in the amplitude-frequency characteristics of the transformer windings are judged by the correlation coefficient.

7.2 Longitudinal comparison method

The longitudinal comparison method refers to comparing the amplitude-frequency response characteristics of the same transformer, the same winding, the same tap position, the different periods;

7.3 Lateral comparison method

The lateral comparison method refers to comparing the amplitude-frequency response characteristics of three-phase windings of the same voltage level of the transformer. If necessary, the amplitude-frequency response characteristics of the same model transformer manufactured by the same manufacturer at the same time are used to judge whether the transformer winding is deformed. This method does not require the original amplitude-frequency response characteristics of the transformer;

7.4 Comprehensive analysis method

The comprehensive analysis method mainly compares the three-phase frequency response fingerprints of the transformer laterally and longitudinally; makes a judgment based on the differences in the three-phase frequency response fingerprints.

See Appendix F for an example of using the comprehensive comparison method to judge the deformation of the transformer winding.

7.5 Analysis process

7.6 Winding deformation analysis

7.6.1 The typical amplitude-frequency response characteristic curve of transformer

winding usually contains multiple obvious peaks and troughs. The changes in the distribution position and number of peaks or troughs are important bases for analyzing transformer winding deformation. See Appendix I for the typical amplitude-frequency response characteristic curve of transformer winding deformation.

......

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 11 pages — is available in the English PDF.

Referenced standards

How to Download DL/T 911-2016

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
11 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

DL/T 911-2016

$195.00