CJ/T 188-2018Technical requirements of utility meters data transmission (English PDF)

Preview PDF

Also coversCJT188-2018

This is a limited preview

Buy now to download the full PDF (17 pages)

Need quotation for your management?

Get a formal quotation for CJ/T 188-2018 in 30 minutes.

Issued by

Ministry of Housing and Urban-Rural Development of PRC

Level / Type

National · Recommended

Issue date

March 8, 2018

Implementation date

October 1, 2018

Scope

CJ/T 188-2018 (Technical requirements of utility meters data transmission) is available as an English-translated PDF.

CJ/T 188-2018 is the Chinese standard "Technical requirements of utility meters data transmission". Its scope clause reads: This standard specifies the functional requirements, physical layer, data link layer, data security, application layer for data transmission of household metering instruments (hereinafter referred to as meters).

This standard is applicable to the automatic reading system, for data exchange between the master station and the slave station, one master and one slave, or one master and multiple slaves.

Its clauses include terms and definitions; functional requirements; physical layer; data-link layer; data security; application layer. It was issued by the Ministry of Housing and Urban-Rural Development of PRC on 2018-03-08 and took effect on 2018-10-01.

Found what you need?

Document preview — CJ/T 188-2018

National Standard of the People's Republic of China

ICS
35.240.99
Classification
L 78

Issued by: Ministry of Housing and Urban-Rural Development of PRC

Contents

  • Foreword...3
  • 1 Scope...5
  • 2 Normative references...5
  • 3 Terms and definitions...6
  • 4 Functional requirements...7
  • 5 Physical layer...10
  • 6 Data-link layer...10
  • 7 Data security...15
  • 8 Application layer...17

1 Scope

This standard specifies the functional requirements, physical layer, data link layer, data security, application layer for data transmission of household metering instruments (hereinafter referred to as meters).

This standard is applicable to the automatic reading system, for data exchange between the master station and the slave station, one master and one slave, or one master and multiple slaves.

2 Normative references

The following documents are essential to the application of this document. For the dated documents, only the versions with the dates indicated are applicable to this document;

for the undated documents, only the latest version (including all the amendments) is applicable to this standard.

GB/T 778.1 Measurement of water flow in fully charged closed conduits - Meters for cold potable water and hot water - Part 1.Specifications

GB/T 6968 Diaphragm gas meters

GB/T 19582.1 Modbus industrial automation network specification - Part 1.

Modbus application protocol

GB/T 19897.1-2005 Automatic meter reading system lower layer communication protocol - Part 1.direct local data exchange

GB/T 26831.2 Society energy metering for reading system specification - Part 2.

Physical and link layer

3 Terms and definitions

The following terms and definitions apply to this document.

3.1

Automatic meter reading system

The system, by which the data of multiple slave stations is read automatically by the master station, through the physical channel, referred to as the automatic meter reading (AMR).

3.2

Master station

A device that selects one, a group or all of the slave stations AND initiates an information exchange with the slave stations. It can be a concentrator, a handheld device, a computer, or other data terminal.

3.3

Slave station

A device, that has a unique identification address in the entire network, receives information from the master station, exchanges information with the master station.

Note. In this standard, it refers to instrument.

3.4

Bus

A physical cline, that connects the master station with multiple slave stations.

4 Functional requirements

4.1 General requirements

4.1.1 The automatic meter reading system shall have the ability to identify different types of slave stations and two-way communication.

4.2 Function of master station

4.2.1 It shall be able to automatically read and receive the data of each slave station, according to the set time; have the functions of real-time random reading and selective reading by address.

4.2.2 It shall be able to set the initial parameters of the master station, such as time, etc.;

there shall be measures to prevent unauthorized personnel from operating.

4.2.3 It shall be able to realize the time calibration of the slave station system.

4.3 Function of slave station

4.3.1 It shall be able to receive and respond to the master station’s reading information.

4.4 Data transmission reliability

4.4.1 The one-time reading success rate is calculated, according to formula (1).

4.5 Meters

4.5.1 The accuracy of the water meter shall comply with the relevant provisions of

GB/T 778.1.

4.5.2 The output parameters of the water meter shall include the current cumulative

4.5.6 The output parameters of the heat (cold) meter shall include real-time time, heating (cooling) volume on settlement day, current heating (cooling) volume, thermal power, instantaneous flow, cumulative flow, water supply temperature, return water temperature, cumulative working time, etc.

5 Physical layer

5.1 Interface form

Instrument communication interfaces include M-Bus interface, RS-485 interface, wireless transceiver interface, optical interface. When using other interfaces, it shall comply with the provisions of relevant standards.

5.4 Wireless transceiver interface

The radio frequency, which is used by the wireless transceiver interface, is preferably the 433 MHz frequency band, the 470MHz frequency band, the 780 MHz frequency band or the 868 MHz frequency band. Transmission power and other main technical indicators shall comply with relevant national requirements.

5.5 Optical interface

6 Data-link layer

6.1 Protocol communication method

This protocol adopts the half-duplex communication mode of master-slave structure.

6.3 Frame format

6.3.1 The frame format shall comply with the provisions of Table 2.

6.3.4 The format of the control code (C) is as shown in Figure 3.

6.3.6 The data field (DATA) includes data identification, serial number, data; its structure changes with the function of the control code.

6.3.7 The check code (CS) is one byte; all bytes, from the frame start character (including the frame start character) to the check code, are accumulated in binary arithmetic, excluding the overflow value which exceeds FFH.

6.4 Transmission requirements

6.4.1 Preamble byte. When using wired interface, 2 bytes ~ 4 bytes FEH shall be sent, before sending frame information.

6.4.4 Error control. If the receiver detects a checksum, even check bit or format error, it shall abandon the information frame and not respond.

6.4.5 Transmission rate. The commonly used rates are 300 bps, 600 bps, 1200 bps, 2400 bps, 4800 bps, 9600 bps.

7 Data security

7.1 Security requirements

It shall comply with the relevant provisions of the national password management.

7.2 Cryptographic algorithms

7.3 Key management

The 16-byte key is defined and managed by the vendor and the user. The key management shall be secure and reliable.

7.4 Data padding

7.4.1 The plaintext data area to be encrypted is the part of the data field (DATA), after removing the data identification DI and the serial number SER. Before data encryption, data padding shall be performed first.

7.5 Data encryption

7.5.1 The padded data is encrypted according to the SM4 encryption algorithm. After the encryption is completed, replace the content of the data field of the frame; modify the data length field and check code to the correct value.

7.6 Data decryption

7.6.1 After receiving the data, the decryption operation shall be performed, according to the SM4 cipher algorithm, which is specified in GM/T 0002-2012.

7.6.2 After the data decryption is completed, the padding content is removed, the original data is restored for data processing.

8 Application layer

8.1 Read operation

8.1.4 The function of the slave station’s abnormal response frame is that the slave station receives the response of the error control code.

8.2 Write operation

8.2.1 During write operation, the serial number SER, which is sent by the master station, is incremented by 1 (modulo 256), before each communication. The response serial number of the slave station shall be the same as the serial number, which is sent by the master station.

8.2.3 The function of the normal response frame of the slave station is to inform the master station of the execution result of the request command.

8.2.5 The coding format of the master station’s request for write operation shall comply with the provisions of Table 15.

......

......
This preview omits tables, figures, formulas and parts of the technical clauses. The complete document — 17 pages — is available in the English PDF.

Referenced standards

How to Download CJ/T 188-2018

  1. 1

    Add to cart

    Click "Download PDF" on this page and choose "Buy this standard". You can add more standards before checkout.

  2. 2

    Checkout

    Enter your email and billing details. Payment is processed securely by Stripe (cards or bank transfer). Prefer bank details? Request a quotation (min. order $300).

  3. 3

    Instant delivery (0–9 sec)

    Delivery is automatic: within seconds of payment you'll receive an email with a secure download link. The link stays valid for 72 hours.

  4. 4

    Invoice included

    A tax invoice is attached to the confirmation email. Need a custom invoice? Contact us.

Related Standards

English PDF
17 pages
Instant delivery (0–9 sec)
Invoice included
View Cart

Secure payment via Stripe

Payments accepted

VisaMastercardAmerican ExpressApple PayGoogle PayStripe

CJ/T 188-2018

$295.00